APC ACRP501, ACRP502, ACRP500, ACRP102, ACRP100 Chilled Water Performance Specifications 10C 50F EWT

Page 24

Chilled Water Performance Specifications 10°C (50°F) EWT

Temperature dry

 

Total Net

Sensible Net

Sensible Heat

 

Total CW

bulb (DB), wet bulb

CW Delta T

CW Flow Rate

Capacity

Capacity

Ratio

Pressure Drop

(WB)

°C (°F)

l/s (GPM)

kW (BTU/hr)

kW (BTU/hr)

SHR

kPa (ft H2O)*

°C (°F)

 

 

 

 

 

 

 

 

 

26.7°C DB, 17.1°C WB

(80°F DB, 62.8°F

WB)

 

 

 

 

 

 

5.5 (10)

32.6 (111,000)

31.8 (109,000)

0.98

1.5 (23.5)

54 (18.02)

 

6.6 (12)

29.9 (102,000)

29.2 (100,000)

0.98

1.1 (18.1)

33

(11.1)

 

7.7 (14)

27.4 (93,000)

26.7 (91,000)

0.98

0.9 (14.3)

21 (6.9)

 

8.8 (16)

24.9 (85,000)

24.3 (83,000)

0.98

0.7 (11.5)

14 (4.6)

 

10 (18)

22.6 (77,000)

22.0 (75,000)

0.98

0.6 (9.4)

10 (3.2)

 

11.1 (20)

20.4 (70,000)

19.9 (68,000)

0.98

0.5 (7.7)

7

(2.3)

29.4°C DB, 18.1°C WB

(85°F DB, 64.5°F

WB)

 

 

 

 

 

 

5.5 (10)

39.6 (135,000)

38.6 (132,000)

0.98

1.8 (28.0)

76

(25.6)

 

6.6 (12)

36.6 (125,000)

35.7 (122,000)

0.98

1.4 (21.8)

47

(15.7)

 

7.7 (14)

33.8 (115,000)

32.9 (112,000)

0.98

1.1 (17.3)

30

(10.2)

 

8.8 (16)

31.1 (106,000)

30.3 (103,000)

0.98

0.9 (14.0)

20 (6.7)

 

10 (18)

28.5 (97,000)

27.7 (95,000)

0.98

0.7 (11.5)

14 (4.6)

 

11.1 (20)

26.0 (89,000)

25.3 (86,000)

0.98

0.6 (9.5)

10 (3.2)

32.2°C DB, 18.9°C WB

(90°F DB, 66.1°F

WB)

 

 

 

 

 

 

6.6 (12)

43.6 (149,000)

43.2 (147,000)

0.99

1.6 (25.6)

64

(21.5)

 

7.7 (14)

40.5 (138,000)

40.1 (137,000)

0.99

1.3 (20.5)

42

(13.9)

 

8.8 (16)

37.6 (128,000)

37.2 (127,000)

0.99

1.1 (16.7)

28 (9.5)

 

10 (18)

34.7 (119,000)

34.4 (117,000)

0.99

0.9 (13.8)

20 (6.5)

 

11.1 (20)

32.0 (109,000)

31.7 (108,000)

0.99

0.7 (11.5)

14 (4.6)

35.0°C DB, 19.8°C WB

(95°F DB, 67.7°F

WB)

 

 

 

 

 

 

6.6 (12)

51.9 (177,000)

51.4 (175,000)

0.99

1.9 (30.1)

88

(29.3)

 

7.7 (14)

48.5 (166,000)

48.0 (164,000)

0.99

1.5 (24.2)

58

(19.4)

 

8.8 (16)

45.3 (155,000)

44.8 (153,000)

0.99

1.3 (19.9)

39

(13.2)

 

10 (18)

42.1 (144,000)

41.7 (142,000)

0.99

1.0 (16.5)

28 (9.2)

 

11.1 (20)

38.7 (132,000)

38.7 (132,000)

1.00

0.9 (13.7)

19 (6.5)

37.8°C DB, 20.7°C WB

(100°F DB, 69.2°F WB)

 

 

 

 

 

 

7.7 (14)

56.7 (194,000)

56.7 (194,000)

1.00

1.8 (28.1)

77

(25.6)

 

8.8 (16)

53.2 (182,000)

53.2 (182,000)

1.00

1.5 (23.1)

53

(17.6)

 

10 (18)

49.8 (170,000)

49.8 (170,000)

1.00

1.2 (19.3)

37

(12.5)

40.6°C DB, 21.6°C WB

(105°F DB, 70.8°F WB)

 

 

 

 

 

 

8.8 (16)

62.3 (213,000)

62.3 (213,000)

1.00

1.7 (26.9)

70

(23.6)

Note: All values are accurate to +/- 5% and based on full speed with standard filters.

Note: Reduce airflow and cooling capacity specifications by 7% for cooling units run at low input voltage (380 V).

Note: Any CW flow rate of 0.19 l/s - 0.32 l/s (3.0 GPM - 5.0 GPM) may cause an increased error in flow rate and power calculation. A fluid flow fault may result. Any flow rate under 0.19 l/s (3.0 GPM) may also display as 0 in the flow rate and power calculation. Note: For sustained operation, a maximimum flow rate of 2.2 l/s (34 GPM) is recommended. This may be exceeded by 25% for peak conditions.

* To convert feet of water to PSIG, use the following formula: ft H2O ÷ 2.307 = PSIG.

20

InRow RP Technical Data Manual

Image 24 Contents
InRow RP American Power Conversion Legal Disclaimer Contents InRow RP Models Overview Scalable Solution for Critical Environments InRow AdvantagesScalable for High Density Hot Aisle Containment System Standard Features Remote Temperature Sensors Dual Position Float Condensate ManagementNetwork Management Card Bay Kit InRow RP NetShelter SXOptional Features Microprocessor Controller Alarms Chilled Water Only AlarmsAir-cooled Only Alarms InRow RP Models Chilled Water Interior Components front of unit Chilled Water Interior Components back of unit Air-cooled Interior Components front of unit Air-cooled Interior Components back of unit Chilled Water and Air-cooled User Interface Connections BMS GNDChilled Water Electrical Panel Air-cooled Electrical Panel Performance Specifications Chilled Water Performance Specifications 5.5C 42F EWTChilled Water Performance Specifications 7.2C 45F EWT GPMChilled Water Performance Specifications 8.9C 48F EWT 29.4C DB, 18.1C WBChilled Water Performance Specifications 10C 50F EWT Chilled Water Performance Specifications 12.8C 55F EWT Chilled Water Performance Specifications 15.5C 60F EWT Chilled Water Data General Modulating ValvesAir-cooled Performance Specifications Glycol Correction FactorsAltitude Correction Factors for InRow Products Air-cooled Data General Sound Performance Data Electrical DataDimensional Data InRow RP Assembled ModuleSX to VX Height Adapter SX to 48U SX Height AdapterChilled Water Piping Diagram Piping and Mechanical ConnectionsTop Chilled Water Piping Access top view FRONT-COLD AisleBottom Chilled Water Piping Access bottom view, looking up Air-cooled Piping Diagram Air-cooled Piping Access top Air-cooled Piping Access bottom view, looking up Air-Cooled Condensers Mechanical DataACCD75201 and ACCD75204 ACCD75202 and ACCD75205 ACCD75203 and ACCD75206Air-cooled Condenser Features ACCD75207ACCD75208 and ACCD75209 Guide Specifications Part 1 GeneralVariable Speed FAN Assembly InRow RP Technical Data Manual Network Management Card Condensate Pump Selectable TOP or Bottom Piping AIR-COOLED only Guidelines for Installation Page APC Worldwide Customer Support 990-2469E-001 2009