APC ACRP501, ACRP502, ACRP500, ACRP102, ACRP100, ACRP101 manual Air-cooled Piping Diagram

Page 36

Air-cooled Piping Diagram

Bottom piping

gas

Condenser

Hot

 

 

Liquid

RP

 

 

Receiver

Top piping

 

gas

Condenser

Hot

 

Liquid

na2543a

RP

Receiver

 

 

 

Note: Shutoff valves shown nearest to the condensers are not supplied by APC.

Pitch in direction of refrigerant flow; 4 mm per m (0.5-in per 10 ft)

Shutoff valves

Head pressure control valve

Check valve

All lines are Type L copper tubing.

Pressure relief valve

P-trap

S-trap

Inverted P-trap

Note: Route piping through the top or bottom of the InRow RP.

Note: Trap the vertical discharge line every 6 m (20 ft) to ensure proper oil return.

Note: The maximum piping run is 61 m (200 ft) equivalent length. Size the piping pursuant to accepted refrigeration practice.

Warning: Do not install the air-cooled condenser below the indoor equipment. The condenser must be positioned above or at the same level as the equipment to ensure proper function.

32

InRow RP Technical Data Manual

Image 36 Contents
InRow RP American Power Conversion Legal Disclaimer Contents InRow RP Models Overview Scalable Solution for Critical Environments InRow AdvantagesScalable for High Density Hot Aisle Containment System Standard Features Remote Temperature Sensors Dual Position Float Condensate ManagementNetwork Management Card Bay Kit InRow RP NetShelter SXOptional Features Microprocessor Controller Alarms Chilled Water Only AlarmsAir-cooled Only Alarms InRow RP Models Chilled Water Interior Components front of unit Chilled Water Interior Components back of unit Air-cooled Interior Components front of unit Air-cooled Interior Components back of unit Chilled Water and Air-cooled User Interface Connections BMS GNDChilled Water Electrical Panel Air-cooled Electrical Panel Performance Specifications Chilled Water Performance Specifications 5.5C 42F EWTChilled Water Performance Specifications 7.2C 45F EWT GPMChilled Water Performance Specifications 8.9C 48F EWT 29.4C DB, 18.1C WBChilled Water Performance Specifications 10C 50F EWT Chilled Water Performance Specifications 12.8C 55F EWT Chilled Water Performance Specifications 15.5C 60F EWT Chilled Water Data General Modulating ValvesAir-cooled Performance Specifications Glycol Correction FactorsAltitude Correction Factors for InRow Products Air-cooled Data General Sound Performance Data Electrical DataDimensional Data InRow RP Assembled ModuleSX to VX Height Adapter SX to 48U SX Height AdapterChilled Water Piping Diagram Piping and Mechanical ConnectionsTop Chilled Water Piping Access top view FRONT-COLD AisleBottom Chilled Water Piping Access bottom view, looking up Air-cooled Piping Diagram Air-cooled Piping Access top Air-cooled Piping Access bottom view, looking up Air-Cooled Condensers Mechanical DataACCD75201 and ACCD75204 ACCD75202 and ACCD75205 ACCD75203 and ACCD75206Air-cooled Condenser Features ACCD75207ACCD75208 and ACCD75209 Guide Specifications Part 1 GeneralVariable Speed FAN Assembly InRow RP Technical Data Manual Network Management Card Condensate Pump Selectable TOP or Bottom Piping AIR-COOLED only Guidelines for Installation Page APC Worldwide Customer Support 990-2469E-001 2009