Air-cooled Piping Diagram
Bottom piping
gas | Condenser | |
Hot | ||
| ||
| Liquid | |
RP |
| |
| Receiver |
Top piping |
| |
gas | Condenser | |
Hot | ||
| ||
Liquid | na2543a |
RP | Receiver |
| |
|
|
Note: Shutoff valves shown nearest to the condensers are not supplied by APC.
Pitch in direction of refrigerant flow; 4 mm per m
Shutoff valves
Head pressure control valve
Check valve
All lines are Type L copper tubing.
Pressure relief valve
Inverted
Note: Route piping through the top or bottom of the InRow RP.
Note: Trap the vertical discharge line every 6 m (20 ft) to ensure proper oil return.
Note: The maximum piping run is 61 m (200 ft) equivalent length. Size the piping pursuant to accepted refrigeration practice.
Warning: Do not install the
32 | InRow RP Technical Data Manual |