APC ACRP502, ACRP501, ACRP500, ACRP102 manual Chilled Water Performance Specifications 12.8C 55F EWT

Page 25

Chilled Water Performance Specifications 12.8°C (55°F) EWT

 

 

 

 

 

 

Total CW

Temperature dry bulb

CW Delta T

Total Net

Sensible Net

Sensible Heat

CW Flow Rate

Pressure

(DB), wet bulb (WB)

Capacity

Capacity

Ratio

Drop

°C (°F)

l/s (GPM)

°C (°F)

kW (BTU/hr)

kW (BTU/hr)

SHR

kPa (ft

 

 

 

 

 

 

H2O)*

26.7°C DB, 17.1°C WB

(80°F DB, 62.8°F

WB)

 

 

 

 

 

 

5.5 (10)

24.7 (85,000)

24.7 (85,000)

1.00

1.2 (18.3)

33

(11.3)

 

6.6 (12)

22.3 (76,000)

22.3 (76,000)

1.00

0.9 (13.9)

20 (6.7)

 

7.7 (14)

20.0 (68,000)

20.0 (68,000)

1.00

0.7 (10.8)

12 (4.2)

 

8.8 (16)

17.8 (61,000)

17.8 (61,000)

1.00

0.5 (8.6)

8

(2.8)

 

10 (18)

15.8 (54,000)

15.8 (54,000)

1.00

0.4 (6.9)

5

(1.8)

 

11.1 (20)

13.9 (48,000)

13.9 (48,000)

1.00

0.4 (5.6)

4

(1.2)

29.4°C DB, 18.1°C WB

(85°F DB, 64.5°F

WB)

 

 

 

 

 

 

5.5 (10)

31.3 (107,000)

31.3 (107,000)

1.00

1.4 (22.6)

50

(16.9)

 

6.6 (12)

28.5 (97,000)

28.5 (97,000)

1.00

1.1 (17.3)

30

(10.2)

 

7.7 (14)

25.8 (88,000)

25.8 (88,000)

1.00

0.9 (13.6)

19 (6.5)

 

8.8 (16)

23.3 (80,000)

23.3 (80,000)

1.00

0.7 (10.8)

8

(4.2)

 

10 (18)

21.0 (72,000)

21.0 (72,000)

1.00

0.6 (8.8)

8

(2.8)

 

11.1 (20)

18.7 (64,000)

18.7 (64,000)

1.00

0.5 (7.2)

6

(1.8)

32.2°C DB, 18.9°C WB

(90°F DB, 66.1°F

WB)

 

 

 

 

 

 

5.5 (10)

39.1 (133,000)

39.1 (133,000)

1.00

1.7 (27.7)

75

(24.9)

 

6.6 (12)

35.9 (123,000)

35.9 (123,000)

1.00

1.3 (21.3)

45 (15.02)

 

7.7 (14)

32.8 (112,000)

32.8 (112,000)

1.00

1.1 (16.9)

29 (9.7)

 

8.8 (16)

30.0 (102,000)

30.0 (102,000)

1.00

0.9 (13.6)

19 (6.5)

 

10 (18)

27.2 (93,000)

27.2 (93,000)

1.00

0.7 (11.1)

13 (4.4)

35.0°C DB, 19.8°C WB

(95°F DB, 67.7°F

WB)

 

 

 

 

 

 

6.6 (12)

44.2 (151,000)

44.2 (151,000)

1.00

1.6 (25.9)

66

(21.9)

 

7.7 (14)

40.8 (139,000)

40.8 (139,000)

1.00

1.3 (20.6)

42

(14.1)

 

8.8 (16)

37.5 (128,000)

37.5 (128,000)

1.00

1.1 (16.7)

28 (9.5)

37.8°C DB, 20.7°C WB (100°F DB, 69.2°F WB)

7.7 (14)

49.8 (170,000)

49.8 (170,000)

40.6°C DB, 21.6°C WB (105°F DB, 70.8°F WB)

1.00

1.6 (24.8)

60 (20.1)

7.7 (14)

59.7 (204,000)

59.7 (204,000)

1.00

1.9 (29.5)

84 (28.2)

Note: All values are accurate to +/- 5% and based on full speed with standard filters.

Note: Reduce airflow and cooling capacity specifications by 7% for cooling units run at low input voltage (380 V).

Note: Any CW flow rate of 0.19 l/s - 0.32 l/s (3.0 GPM - 5.0 GPM) may cause an increased error in flow rate and power calculation. A fluid flow fault may result. Any flow rate under 0.19 l/s (3.0 GPM) may also display as 0 in the flow rate and power calculation. Note: For sustained operation, a maximimum flow rate of 2.2 l/s (34 GPM) is recommended. This may be exceeded by 25% for peak conditions.

* To convert feet of water to PSIG, use the following formula: ft H2O ÷ 2.307 = PSIG.

InRow RP Technical Data Manual

21

Image 25 Contents
InRow RP American Power Conversion Legal Disclaimer Contents InRow RP Models Overview InRow Advantages Scalable Solution for Critical EnvironmentsScalable for High Density Hot Aisle Containment System Standard Features Dual Position Float Condensate Management Remote Temperature SensorsNetwork Management Card Bay Kit InRow RP NetShelter SXOptional Features Microprocessor Controller Chilled Water Only Alarms AlarmsAir-cooled Only Alarms InRow RP Models Chilled Water Interior Components front of unit Chilled Water Interior Components back of unit Air-cooled Interior Components front of unit Air-cooled Interior Components back of unit BMS GND Chilled Water and Air-cooled User Interface ConnectionsChilled Water Electrical Panel Air-cooled Electrical Panel Chilled Water Performance Specifications 5.5C 42F EWT Performance SpecificationsGPM Chilled Water Performance Specifications 7.2C 45F EWT29.4C DB, 18.1C WB Chilled Water Performance Specifications 8.9C 48F EWTChilled Water Performance Specifications 10C 50F EWT Chilled Water Performance Specifications 12.8C 55F EWT Chilled Water Performance Specifications 15.5C 60F EWT Modulating Valves Chilled Water Data GeneralGlycol Correction Factors Air-cooled Performance SpecificationsAltitude Correction Factors for InRow Products Air-cooled Data General Electrical Data Sound Performance DataInRow RP Assembled Module Dimensional DataSX to 48U SX Height Adapter SX to VX Height AdapterPiping and Mechanical Connections Chilled Water Piping DiagramFRONT-COLD Aisle Top Chilled Water Piping Access top viewBottom Chilled Water Piping Access bottom view, looking up Air-cooled Piping Diagram Air-cooled Piping Access top Air-cooled Piping Access bottom view, looking up Mechanical Data Air-Cooled CondensersACCD75203 and ACCD75206 ACCD75201 and ACCD75204 ACCD75202 and ACCD75205ACCD75207 Air-cooled Condenser FeaturesACCD75208 and ACCD75209 Part 1 General Guide SpecificationsVariable Speed FAN Assembly InRow RP Technical Data Manual Network Management Card Condensate Pump Selectable TOP or Bottom Piping AIR-COOLED only Guidelines for Installation Page 990-2469E-001 2009 APC Worldwide Customer Support