APC ACRP101, ACRP501, ACRP502, ACRP500, ACRP102, ACRP100 manual Air-cooled Data General

Page 29

Air-cooled Data - General

MODEL

ACRP 100 Series

AIR SYSTEM - FAN (Standard Filter Installed)

 

Air Volume - l/s (SCFM)

2265 (4800)

Fan Motor - W (HP)

1100 (1.5)

Number of Fans

2

COOLING COIL - COPPER TUBE/ALUMINUM FIN

 

Face Area - m2 (ft2)

.56 (6.0)

Rows Deep

4

HUMIDIFICATION - SOLID STATE ELECTRODE CANISTER

 

Flush Cycle

automatic

Capacity - kg/hr (lbs/hr)

3 (6.6)

kW

2.25

REHEAT

 

Electric - Equally Loaded Two Stage, Finned Tubular, Low-Watt Density

 

Capacity - kW (BTU/hr)

6 (20,500)

Stages

2

FILTERS - PLEATED (STANDARD)

 

Quantity

3

Size - mm (in)

418 x 470 (16.45 x 18.5)

Depth - mm (in)

96 (3.78)

Efficiency (%)

30

FILTERS - PLEATED (OPTIONAL)

 

Quantity

3

Size - mm (in)

418 x 470 (16.45 x 18.5)

Depth - mm (in)

96 (3.78)

Efficiency (%)

85

PHYSICAL DATA

 

Weight - kg (lbs)

378 (833)

Height - mm (in)

1991 (78.40)

Width - mm (in)

600 (23.62)

Depth - mm (in)

1070 (42.13)

CONNECTION SIZES

 

Refrigerant

 

Discharge

7/8 in ODF brazed

Maximum pressure drop - bar (PSI)

0.7 (10)

Liquid

7/8 in ODF brazed

Humidifier

 

Supply Line - mm (in)

6.35 (1/4)

Condensate Drain

 

Drain Line - mm (in)

12.7 (1/2)

Note: Reduce airflow and cooling capacity specifications by 7% for cooling units run at low input voltage (380 V).

InRow RP Technical Data Manual

25

Image 29 Contents
InRow RP American Power Conversion Legal Disclaimer Contents InRow RP Models Overview Scalable for High Density Scalable Solution for Critical EnvironmentsInRow Advantages Hot Aisle Containment System Standard Features Dual Position Float Condensate Management Remote Temperature SensorsNetwork Management Card Bay Kit InRow RP NetShelter SXOptional Features Microprocessor Controller Air-cooled Only Alarms AlarmsChilled Water Only Alarms InRow RP Models Chilled Water Interior Components front of unit Chilled Water Interior Components back of unit Air-cooled Interior Components front of unit Air-cooled Interior Components back of unit BMS GND Chilled Water and Air-cooled User Interface ConnectionsChilled Water Electrical Panel Air-cooled Electrical Panel Chilled Water Performance Specifications 5.5C 42F EWT Performance SpecificationsGPM Chilled Water Performance Specifications 7.2C 45F EWT29.4C DB, 18.1C WB Chilled Water Performance Specifications 8.9C 48F EWTChilled Water Performance Specifications 10C 50F EWT Chilled Water Performance Specifications 12.8C 55F EWT Chilled Water Performance Specifications 15.5C 60F EWT Modulating Valves Chilled Water Data GeneralAltitude Correction Factors for InRow Products Air-cooled Performance SpecificationsGlycol Correction Factors Air-cooled Data General Electrical Data Sound Performance DataInRow RP Assembled Module Dimensional DataSX to 48U SX Height Adapter SX to VX Height AdapterPiping and Mechanical Connections Chilled Water Piping DiagramFRONT-COLD Aisle Top Chilled Water Piping Access top viewBottom Chilled Water Piping Access bottom view, looking up Air-cooled Piping Diagram Air-cooled Piping Access top Air-cooled Piping Access bottom view, looking up Mechanical Data Air-Cooled CondensersACCD75203 and ACCD75206 ACCD75201 and ACCD75204 ACCD75202 and ACCD75205ACCD75208 and ACCD75209 Air-cooled Condenser FeaturesACCD75207 Part 1 General Guide SpecificationsVariable Speed FAN Assembly InRow RP Technical Data Manual Network Management Card Condensate Pump Selectable TOP or Bottom Piping AIR-COOLED only Guidelines for Installation Page 990-2469E-001 2009 APC Worldwide Customer Support
Related manuals