APC ACRP502, ACRP501, ACRP500, ACRP102, ACRP100, ACRP101 manual Variable Speed FAN Assembly

Page 43

B.VARIABLE SPEED FAN ASSEMBLY

1. Variable Speed Fans: The unit is equipped with variable speed, electronically commutated, 400 mm backward incline fans complete with Inlet Volute.

2. Fan Protection: discharge finger guard. Outlet of the fan should include a cage type finger guard.

C.AUTOMATIC TRANSFER SWITCH (CHILLED WATER ONLY)

The unit shall be equipped with an automatic transfer switch (ATS). The ATS shall automatically switch from a main power supply to a secondary power supply in the event of a power outage without change in equipment operation. The ATS shall monitor the main power supply so that when the power is restored to the primary source it will automatically switch from the secondary source back to the main power source.

D.MAIN DISCONNECT SWITCH

1. Unit shall be provided with Thermal-Magnetic circuit breakers with interrupt capacity ratings per UL489/CSA C22.2/IEC-947.

Voltage

kAIC

 

 

200-240V 50/60Hz

50

 

 

380-415V 50Hz

36

 

 

460-480V 60Hz

22

 

 

2 . Chilled Water: Units shall include main disconnect switches located on the E-panel in order to individually disconnect dual A-B power inputs.

3 . Air-cooled: Units shall include a main disconnect switch located on the E-panel in order to disconnect power input.

4 . A condenser disconnect shall be field-supplied.

E.MICROPROCESSOR CONTROLLER

1. Monitoring and Configuration: The display shall allow monitoring and configuration of the air

conditioning unit through a menu-based control. Functions include status reporting, set-up, and temperature set points. Four LEDs report the operational status of the connected air conditioning unit.

2. Controls: The microprocessor controller shall come equipped with control keys to allow the user to navigate between menus, select items, and input alpha numeric information.

3. Alarms: The microprocessor controller shall activate a visible and audible alarm in the occurrence of the following events:

a.Cool Fail

b.Rack inlet temperature violation

c.Rack inlet temperature sensor fault

d.Air filter clogged

e.Air filter run hours exceeded

f.Filter DP sensor failure

g.Supply air sensor fault

h.Return air sensor fault

i.Supply air high temperature violation

j.Return air high temperature violation

InRow RP Technical Data Manual

39

Image 43 Contents
InRow RP American Power Conversion Legal Disclaimer Contents InRow RP Models Overview InRow Advantages Scalable Solution for Critical EnvironmentsScalable for High Density Hot Aisle Containment System Standard Features Bay Kit InRow RP NetShelter SX Remote Temperature SensorsDual Position Float Condensate Management Network Management CardOptional Features Microprocessor Controller Chilled Water Only Alarms AlarmsAir-cooled Only Alarms InRow RP Models Chilled Water Interior Components front of unit Chilled Water Interior Components back of unit Air-cooled Interior Components front of unit Air-cooled Interior Components back of unit BMS GND Chilled Water and Air-cooled User Interface ConnectionsChilled Water Electrical Panel Air-cooled Electrical Panel Chilled Water Performance Specifications 5.5C 42F EWT Performance SpecificationsGPM Chilled Water Performance Specifications 7.2C 45F EWT29.4C DB, 18.1C WB Chilled Water Performance Specifications 8.9C 48F EWTChilled Water Performance Specifications 10C 50F EWT Chilled Water Performance Specifications 12.8C 55F EWT Chilled Water Performance Specifications 15.5C 60F EWT Modulating Valves Chilled Water Data GeneralGlycol Correction Factors Air-cooled Performance SpecificationsAltitude Correction Factors for InRow Products Air-cooled Data General Electrical Data Sound Performance DataInRow RP Assembled Module Dimensional DataSX to 48U SX Height Adapter SX to VX Height AdapterPiping and Mechanical Connections Chilled Water Piping DiagramFRONT-COLD Aisle Top Chilled Water Piping Access top viewBottom Chilled Water Piping Access bottom view, looking up Air-cooled Piping Diagram Air-cooled Piping Access top Air-cooled Piping Access bottom view, looking up Mechanical Data Air-Cooled CondensersACCD75203 and ACCD75206 ACCD75201 and ACCD75204 ACCD75202 and ACCD75205ACCD75207 Air-cooled Condenser FeaturesACCD75208 and ACCD75209 Part 1 General Guide SpecificationsVariable Speed FAN Assembly InRow RP Technical Data Manual Network Management Card Condensate Pump Selectable TOP or Bottom Piping AIR-COOLED only Guidelines for Installation Page 990-2469E-001 2009 APC Worldwide Customer Support