APC Glycol Correction Factors and Guidelines for Propylene Glycol in ACRP502 Water Dispenser

Page 28

Glycol Correction Factors

Performance Criteria

Glycol Solution

 

 

Percent Weight of Solution ***

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

10%

 

20%

30%

 

40%

50%

 

 

 

 

 

 

 

 

 

 

Capacity*

Ethylene

1.00

0.97

 

0.93

0.88

 

0.81

0.75

 

 

 

 

 

 

 

 

 

 

 

Propylene

1.00

0.96

 

0.90

0.82

 

0.77

0.74

 

 

 

 

 

 

 

 

 

 

Pressure Drop**

Ethylene

1.00

1.04

 

1.13

1.21

 

1.31

1.41

 

 

 

 

 

 

 

 

 

 

 

Propylene

1.00

1.09

 

1.20

1.35

 

1.52

1.67

 

 

 

 

 

 

 

 

 

 

All correction factors are based on unit entering conditions of 29.4°C (85°F) DB, 18.1 °C (64.5°F) WB, 1368.6 L/S (6950 CFM), 1.72 L/S (27.3 GPM), and 7.2°C (45°F) EFT.

*Multiply capacity of device or system by factor above for % solution. **Multiply pressure drop of system by factor above for % solution.

***Glycol concentrations over 50% are not recommended.

Altitude Correction Factors for InRow Products

Room Condition: 72 DB/50% RH

 

 

 

 

 

 

 

 

 

 

Altitude - m (ft)

0

305

610

915

1219

1524

1829

2134

2438

2743

3048

Specific volume - cm3/g

 

(1000)

(2000)

(3000)

(4000)

(5000)

(6000)

(7000)

(8000)

(9000)

(10000)

847.77

879.61

912.70

947.66

983.86

1021.32

1061.28

1103.10

1146.80

1193.00

1241.69

(ft3/lb)

(13.58)

(14.09)

(14.62)

(15.18)

(15.76)

(16.36)

(17.00)

(17.67)

(18.37)

(19.11)

(19.89)

Density - g/m3 (lb/ft3)

1185.37

1137.31

1089.26

1057.22

1009.16

977.13

945.10

913.05

865.00

832.97

800.92

 

(0.074)

(0.071)

(0.068)

(0.066)

(0.063)

(0.061)

(0.059)

(0.057)

(0.054)

(0.052)

(0.050)

 

 

 

 

 

 

 

 

 

 

 

 

Density Ratio

1.000

0.964

0.929

0.895

0.862

0.830

0.799

0.769

0.739

0.711

0.683

Capacity Correction

1.000

0.981

0.962

0.933

0.913

0.884

0.865

0.846

0.826

0.807

0.787

Density ratio is used for air flow correction factor.

 

 

 

 

 

 

 

 

Capacity correction is used for performance derate.

 

 

 

 

 

 

 

 

Air-cooled Performance Specifications

NET COOLING CAPACITY

 

Entering Air Temperature

ACRP 100 Series

22.2°C DB, 15.5°C WB (72°F DB, 60°F WB)

 

Total - kW (BTU/hr)

22.8 (78,000)

Sensible - kW (BTU/hr)

19.0 (65,000)

23.9°C DB, 16.2°C WB (75°F DB, 61.1°F WB)

 

Total - kW (BTU/hr)

25.2 (86,000)

Sensible - kW (BTU/hr)

21.7 (74,000)

26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB)

 

Total - kW (BTU/hr)

26.9 (92,000)

Sensible - kW (BTU/hr)

26.9 (92,000)

29.4°C DB, 18.1°C WB (85°F DB, 64.6°F WB)

 

Total - kW (BTU/hr)

29.0 (99,000)

Sensible - kW (BTU/hr)

29.0 (99,000)

32.2°C DB, 19.0°C WB (90°F DB, 66.2°F WB)

 

Total - kW (BTU/hr)

30.5 (104,000)

Sensible - kW (BTU/hr)

30.5 (104,000)

35.0°C DB, 19.9°C WB (95°F DB, 67.8°F WB)

 

Total - kW (BTU/hr)

33.7 (115,000)

Sensible - kW (BTU/hr)

33.7 (115,000)

37.8°C DB, 20.7°C WB (100°F DB, 69.3°F WB)

 

Total - kW (BTU/hr)

36.9 (126,000)

Sensible - kW (BTU/hr)

36.9 (126,000)

40.6°C DB, 21.6°C WB) (105°F DB, 70.8°F WB*

 

Total - kW (BTU/hr)

36.6 (125,000)

Sensible - kW (BTU/hr)

36.6 (125,000)

*Airflow reduced to 4000 SCFM at this condition to maintain adequate return gas temperature.

 

Note: Unit is not recommended for use with total loads of 10 kW or less.

 

Note: Shaded lines represent leaving air temperatures above ASHRAE specifications of 25°C (77º F) at maximum airflow.

Note: Reduce airflow and cooling capacity specifications by 7% for cooling units run at low input voltage (380 V).

24

InRow RP Technical Data Manual

Image 28 Contents
InRow RP American Power Conversion Legal Disclaimer Contents InRow RP Models Overview InRow Advantages Scalable Solution for Critical EnvironmentsScalable for High Density Hot Aisle Containment System Standard Features Remote Temperature Sensors Dual Position Float Condensate ManagementNetwork Management Card Bay Kit InRow RP NetShelter SXOptional Features Microprocessor Controller Chilled Water Only Alarms AlarmsAir-cooled Only Alarms InRow RP Models Chilled Water Interior Components front of unit Chilled Water Interior Components back of unit Air-cooled Interior Components front of unit Air-cooled Interior Components back of unit Chilled Water and Air-cooled User Interface Connections BMS GNDChilled Water Electrical Panel Air-cooled Electrical Panel Performance Specifications Chilled Water Performance Specifications 5.5C 42F EWTChilled Water Performance Specifications 7.2C 45F EWT GPMChilled Water Performance Specifications 8.9C 48F EWT 29.4C DB, 18.1C WBChilled Water Performance Specifications 10C 50F EWT Chilled Water Performance Specifications 12.8C 55F EWT Chilled Water Performance Specifications 15.5C 60F EWT Chilled Water Data General Modulating ValvesGlycol Correction Factors Air-cooled Performance SpecificationsAltitude Correction Factors for InRow Products Air-cooled Data General Sound Performance Data Electrical DataDimensional Data InRow RP Assembled ModuleSX to VX Height Adapter SX to 48U SX Height AdapterChilled Water Piping Diagram Piping and Mechanical ConnectionsTop Chilled Water Piping Access top view FRONT-COLD AisleBottom Chilled Water Piping Access bottom view, looking up Air-cooled Piping Diagram Air-cooled Piping Access top Air-cooled Piping Access bottom view, looking up Air-Cooled Condensers Mechanical DataACCD75201 and ACCD75204 ACCD75202 and ACCD75205 ACCD75203 and ACCD75206ACCD75207 Air-cooled Condenser FeaturesACCD75208 and ACCD75209 Guide Specifications Part 1 GeneralVariable Speed FAN Assembly InRow RP Technical Data Manual Network Management Card Condensate Pump Selectable TOP or Bottom Piping AIR-COOLED only Guidelines for Installation Page APC Worldwide Customer Support 990-2469E-001 2009