APC ACRP102, ACRP501, ACRP502, ACRP500, ACRP100, ACRP101 manual Network Management Card

Page 45

ba. Air flow decreased while compressor off

bb.Suction pressure sensor failure bc. Discharge pressure sensor failure bd. High pressure switch active

be. Fan speed decreased to avoid high pressure (event only)

bf. Compressor speed decreased to avoid high pressure (event only) bg. Compressor high pressure

bh. Oil return pump active

4 . Logging: The microprocessor controller shall log and display all available events. Each alarm log shall contain time/date stamp as well as operating conditions at the time of occurrence. Controller shall display the run time hours for major components.

F. NETWORK MANAGEMENT CARD

The unit shall include a network management card to provide management through a computer network through TCP/IP. Management through the network should include the ability to change set points as well as view and clear alarms.

G.COOLING COIL AND CONDENSATE PAN

1. Chilled Water: Cooling coil shall use raised lance type corrugated aluminum fin and (12.7 mm (1/2 in) OD copper tube coils. Fin shall be a minimum of 0.0055 in thick. Tube wall shall be a minimum of 0.016 in thick. Coil tube sheets shall be a minimum 1.2 mm (18 gauge) G90 galvanized steel. Coil shall be rated for a maximum pressure of 2757.9 kPa (400 psig). Coil headers are equipped with drip plates in the bottom to route the condensate accumulating on the header tubes to the condensation pan. Coil is configured in a counterflow arrangement to optimize heat transfer efficiency.

2. Direct Expansion: Cooling coil shall use raised lance type corrugated aluminum fin and 12.7 mm (1/2 in) OD copper tube coils. Fin shall be a minimum of 0.0055 in thick. Tube wall shall be a minimum of 0.016 in thick. Coil end supports shall be a minimum 1.2 mm

(18 gauge) G90 galvanized steel. Coil shall be rated for a maximum pressure of 3447.3 kPa (500 psig), and the coils are certified in accordance with UL207. Coil header is equipped with a drip plate in the bottom to capture and direct the condensation accumulating on the suction header tube to the drain pan. Coil has 6 circuits complete with brass distributor and copper distribution tubes.

H.VARIABLE SPEED COMPRESSOR / VFD ASSEMBLY (AIR-COOLED ONLY)

1. Compressor: The unit shall be configured with a variable speed reciprocating hermetic compressor using a matched VFD. As a result, the compressor speed can be varied through a range between 30 and 85 Hz to accommodate varying load conditions. VFD firmware is written to include oil return protection in cases where pipe velocities may drop to low speeds during low loading periods.

2. Compressor is electrically protected through the VFD.

3. Compressor utilizes a noise cap for noise reduction.

4. Sight glass provided for air cooled system oil charging.

I.3-WAY MODULATING VALVE (CHILLED WATER ONLY)

1. A floating point valve shall be microprocessor controlled to automatically direct the proper amount of chilled water in the cooling coil to maintain desired conditions. A shut-off valve located in the bypass line may be manually adjusted for 2-way flow if so desired.

2. Three way control valve shall be rated for 300 WOG with brass body and stainless steel ball.

3. Valve Actuator: Actuator shall be direct connect rotary floating point style actuator with potentiometer feedback, and should be capable of being replaced without disconnecting piping from the valve. Ability for manual operation is also provided.

InRow RP Technical Data Manual

41

Image 45 Contents
InRow RP American Power Conversion Legal Disclaimer Contents InRow RP Models Overview Scalable Solution for Critical Environments InRow AdvantagesScalable for High Density Hot Aisle Containment System Standard Features Dual Position Float Condensate Management Remote Temperature SensorsNetwork Management Card Bay Kit InRow RP NetShelter SXOptional Features Microprocessor Controller Alarms Chilled Water Only AlarmsAir-cooled Only Alarms InRow RP Models Chilled Water Interior Components front of unit Chilled Water Interior Components back of unit Air-cooled Interior Components front of unit Air-cooled Interior Components back of unit BMS GND Chilled Water and Air-cooled User Interface ConnectionsChilled Water Electrical Panel Air-cooled Electrical Panel Chilled Water Performance Specifications 5.5C 42F EWT Performance SpecificationsGPM Chilled Water Performance Specifications 7.2C 45F EWT29.4C DB, 18.1C WB Chilled Water Performance Specifications 8.9C 48F EWTChilled Water Performance Specifications 10C 50F EWT Chilled Water Performance Specifications 12.8C 55F EWT Chilled Water Performance Specifications 15.5C 60F EWT Modulating Valves Chilled Water Data GeneralAir-cooled Performance Specifications Glycol Correction FactorsAltitude Correction Factors for InRow Products Air-cooled Data General Electrical Data Sound Performance DataInRow RP Assembled Module Dimensional DataSX to 48U SX Height Adapter SX to VX Height AdapterPiping and Mechanical Connections Chilled Water Piping DiagramFRONT-COLD Aisle Top Chilled Water Piping Access top viewBottom Chilled Water Piping Access bottom view, looking up Air-cooled Piping Diagram Air-cooled Piping Access top Air-cooled Piping Access bottom view, looking up Mechanical Data Air-Cooled CondensersACCD75203 and ACCD75206 ACCD75201 and ACCD75204 ACCD75202 and ACCD75205Air-cooled Condenser Features ACCD75207ACCD75208 and ACCD75209 Part 1 General Guide SpecificationsVariable Speed FAN Assembly InRow RP Technical Data Manual Network Management Card Condensate Pump Selectable TOP or Bottom Piping AIR-COOLED only Guidelines for Installation Page 990-2469E-001 2009 APC Worldwide Customer Support