Trane SYS-APM001-EN manual Primary-Secondary Decoupled Systems, Hydraulic decoupling

Page 51

System Configurations

percent of the system load. At system loads greater than 50 percent, the upstream chiller is preferentially loaded because it will attempt to produce the design leaving chilled-water temperature. Any portion of the load that remains is directed to the downstream chiller.

If chiller setpoints are staggered (upstream at 49°F [9.4°C] and downstream at 42°F [5.5°C]), the downstream chiller is loaded first. The upstream machine then meets any portion of the system load that the downstream chiller cannot meet. This control strategy offers several benefits. The first is that the upstream chiller is always operating at an elevated temperature. This allows it to operate at a higher efficiency. Also, placing an absorption chiller in the upstream position increases its capacity. As an example, an absorption chiller that can produce 500 tons [1,760 kW] at a leaving chilled-water temperature of 44°F [6.6°C] may produce 600 tons [2,110 kW] at 50°F [10°C]. Centrifugal, helical-rotary, reciprocating, and scroll chillers experience capacity and efficiency changes to a lesser degree. By judicious use of the series configuration, these benefits can provide reduced installed cost and fuel flexibility to the building owner. While not shown, a single manual bypass with proper valving can provide for servicing of chillers.

Equal loading of the two chillers may be accomplished by using a chiller plant management system to dynamically reset the upstream chiller’s setpoint in response to changes in system load.

Primary–Secondary (Decoupled) Systems

The root cause of the difficulties with parallel chiller control in a constant volume system is the fixed relationship between chiller- and system-flow rates. If, instead, we can hydraulically decouple the production (chiller) piping from the distribution (load) piping, it is possible to control them separately. The fixed relationships are then broken apart. The production pumps are typically constant volume, while the distribution pumps are variable volume.

Hydraulic decoupling

Figure 28 shows the basic decoupled system. This strategy is also referred to as a primary–secondary pumping arrangement. Separate pumps are dedicated to production and distribution. While the same water is pumped twice (by different pumps), there is no duplication of pumping energy. This is because the production pumps overcome only the chiller and production- side pressure drop while the distribution pumps overcome only the distribution system pressure drop.

SYS-APM001-EN

Chiller System Design and Control

45

Image 51
Contents May Page Chiller System Design and Control Preface Contents 100 Chiller Primary System ComponentsChiller evaporator Primary System ComponentsEffect of chilled-water flow rate and variation Effect of chilled-water temperatureEffect of condenser-water temperature Water-cooled condenserEffect of condenser-water flow rate Packaged or Split System? MaintenanceAir-cooled condenser Air-cooled versus water-cooled condensersEnergy efficiency Low-ambient operationAir-cooled or water-cooled efficiency LoadsTwo-way valve load control Three-way valve load controlFace-and-bypass dampers Variable-speed pump load controlChilled-water pump Chilled-Water Distribution SystemDistribution piping Pump per chillerManifolded pumps Constant flow system Pumping arrangementsVariable-primary system Condenser-Water SystemCooling tower Primary-secondary systemSingle tower per chiller Condenser-water pumping arrangementsEffect of load on cooling tower performance Effect of ambient conditions on cooling tower performanceUnit-Level Controls Chiller controlRecommended chiller-monitoring points per Ashrae Standard Centrifugal chiller with AFD Centrifugal chiller capacity controlAFD on both chillers Small Chilled-Water Systems 1-2 chillers Application ConsiderationsApplication Considerations Constant flow Variable flowCondensing method Part load system operation Application ConsiderationsNumber of chillers Parallel or seriesMid-Sized Chilled-Water Systems Chillers Managing control complexityPreferential vs. equalized loading and run-time Large Chilled-Water Systems + Chillers, District Cooling Large chilled-water system schematicPower Pipe sizeWater Controls Chiller performance testingLimitations of field performance testing Chiller Plant System PerformanceSYS-APM001-EN SYS-APM001-EN Guidance for Chilled- and Condenser-Water Flow Rates System Design OptionsChilled-Water Temperatures Standard rating temperaturesSystem Design Options Condenser-Water Temperatures Chilled- and Condenser-Water Flow RatesStandard rating flow conditions System Design Options Selecting flow rates Low-flow conditions for cooling tower Base Case Low Flow DP2/DP1 = Flow2/Flow11.85System summary at full load Total system power Component Power kW Base Case Low FlowChilled water system performance at part load Coil response to decreased entering water temperatureSystem design Entering fluid temperature, F CCooling-tower options with low flow Smaller towerSame tower, smaller approach ΔT2 = 99.1 78 = 21.1F or 37.3 25.6 = 11.7CSame tower, smaller approach Present Smaller Approach Same tower, larger chillerRetrofit capacity changes Larger Present Chiller Same tower Retrofit opportunitiesCost Implications Misconception 1-Low flow is only good for long piping runs Misconceptions about Low-Flow RatesKWh SYS-APM001-EN Parallel Chillers System ConfigurationsParallel chillers with separate, dedicated chiller pumps System ConfigurationsSeries chillers Series ChillersHydraulic decoupling Primary-Secondary Decoupled SystemsCheck valves Production loop System Configurations ProductionDistribution-loop benefits of decoupled system arrangement System Configurations DistributionCommon CampusTertiary or distributed Tertiary pumping arrangement Decoupled system-principle of operationTemperature-sensing Flow-based controlFlow-sensing Multiple chilled-water plants on a distribution loop Adding a chillerSubtracting a chiller Double-ended decoupled system Pump control in a double-ended decoupled systemChiller sequencing in a double-ended decoupled system Other plant designs Variable-Primary-Flow SystemsOperational savings of VPF designs Advantages of variable primary flowDispelling a common misconception Chiller selection requirementsFlow, ft.water Flow rate Flow-rate changes that result from isolation-valve operation Managing transient water flowsSystem Configurations Effect of dissimilar evaporator pressure drops System design and control requirementsAccurate flow measurement Bypass flow control Chiller sequencing in VPF systemsFlow-rate-fluctuation examples Adding a chiller in a VPF systemSequencing based on load Subtracting a chiller in a VPF systemSelect slow-acting valves to control the airside coils Other VPF control considerationsConsider a series arrangement for small VPF applications Plant configurationChiller selection Guidelines for a successful VPF systemAirside control Plant configurationBypass flow Chiller sequencingPlate-and-frame heat exchanger Heat RecoveryChilled-Water System Variations Condenser Free Cooling or Water EconomizerRefrigerant migration Chilled-Water System VariationsWell, river, or lake water Refrigerant migration chiller in free-cooling modePreferential loading parallel arrangement Preferential LoadingSidestream plate-and-frame heat exchanger Preferential loading sidestream arrangementChilled-Water System Variations Sidestream with alternative fuels or absorptionSidestream system control Preferential loading series arrangementSeries-series counterflow Series-Counterflow ApplicationUnequal Chiller Sizing EvaporatorsCondensers System Issues and Challenges Low ΔT SyndromeAmount of Fluid in the Loop Example System Issues and ChallengesChiller response to changing conditions System response to changing conditionsContingency Minimum capacity requiredType and size of chiller Ancillary equipment System Issues and Challenges Location of equipmentAlternative Energy Sources Water and electrical connectionsPlant Expansion Alternative fuelThermal storage Retrofit Opportunities Applications Outside the Chiller’s RangeFlow rate out of range Precise temperature control System Issues and Challenges Temperatures out of rangePrecise temperature control, multiple chillers Chilled-water pump control Chilled water reset-raising and loweringSystem Controls Chilled-Water System ControlCritical valve reset pump pressure optimization System ControlsNumber of chillers to operate Chillers Difference Condenser-Water System ControlMinimum refrigerant pressure differential VFDs and centrifugal chillers performance at 90% loadCooling-tower-fan control Condenser-water temperature controlChiller-tower energy consumption Chiller-tower energy balanceChiller-tower-pump balance System Controls Variable condenser water flowEffect of chiller load on water pumps and cooling tower fans Decoupled condenser-water systemCDWP-2 Failure recovery Failure RecoveryConclusion Glossary Pumps system GlossaryGlossary Plant. Idea 88th Annual Conference Proceedings 1997 ReferencesEngineering July References102 Ashrae IndexIndex 105 106 Page Trane

SYS-APM001-EN specifications

The Trane SYS-APM001-EN is an advanced control system designed for HVAC (Heating, Ventilation, and Air Conditioning) applications, specifically tailored to enhance energy efficiency and system performance. This comprehensive solution integrates cutting-edge technologies to optimize climate control in commercial and industrial environments.

One of the main features of the SYS-APM001-EN is its intuitive user interface. The system is equipped with a large, easy-to-read display that provides real-time data on system performance, energy usage, and environmental conditions. This user-friendly interface makes it simple for operators to monitor and adjust settings, ensuring optimal comfort levels and efficient energy consumption.

Another key characteristic of the SYS-APM001-EN is its advanced data analytics capabilities. The system collects and analyzes data from various sensors throughout the building, providing insights into occupancy patterns, equipment performance, and energy consumption trends. This data-driven approach allows facility managers to make informed decisions about system adjustments, predictive maintenance, and energy savings.

The SYS-APM001-EN also boasts robust integration capabilities. It can seamlessly connect with a variety of building management systems (BMS) and other third-party devices. This interoperability enables a cohesive operational ecosystem where HVAC systems can communicate and cooperate with lighting, security, and fire safety systems, enhancing overall building efficiency.

Energy efficiency is a hallmark of the SYS-APM001-EN, as it implements sophisticated algorithms to optimize system operation. These algorithms adjust equipment performance in real-time based on current conditions, thereby reducing energy waste and lowering operational costs. The system is designed to support multiple energy-saving strategies, including demand-controlled ventilation and optimal start/stop scheduling.

Additionally, the SYS-APM001-EN is built with scalability in mind, accommodating facilities of various sizes and configurations. Whether it’s a small office building or a large industrial complex, the system can be tailored to meet specific needs, ensuring that HVAC performance aligns with operational goals.

In conclusion, the Trane SYS-APM001-EN is an innovative HVAC control solution that emphasizes user experience, data-driven decision-making, and energy efficiency. With its advanced features and technologies, it is an essential tool for optimizing building performance and enhancing occupant comfort while reducing environmental impact.