Trane SYS-APM001-EN Plant configuration, Consider a series arrangement for small VPF applications

Page 73

System Configurations

For more information, refer to the Trane Engineers Newsletter, Don’t Overlook Optimization Opportunities in ’Small’ Chilled Water Systems” (ADM-APN009- EN).

Plant configuration

Consider a series arrangement for small VPF applications.

When the plant consists of only two chillers and expansion is unlikely, you can simplify control by piping the evaporators in series. Doing so avoids flow transitions because the water always flows through both chillers. The series arrangement requires careful selection because the pump must be sized for the pressure drop through both chillers. However, the extra pressure quickly decreases (by roughly the square of the flow rate) as the flow rate slows. For example, at 80 percent of design flow, the evaporator pressure drop is only 64 percent of design. Given this operating characteristic, a VPF design may permit a slightly higher system pressure drop than a comparable primary– secondary system without a noticeable penalty in operating cost. “Series Chillers” on page 44 discussed these arrangements in greater detail.19

Note: To further reduce the system ΔP, lower the required rate of chilled-water flow through the system by increasing the temperature difference between the supply and return. Plants that supply 40°F [4.4°C] chilled water based on a ΔT of 16°F [8.9°C] or more are increasingly common.

Assess the economic feasibility of VPF for single-chiller plants.

Although most VPF applications consist of two or more chillers, variable primary flow also offers potential operating-cost savings in a new or existing single-chiller plant. Instead of a bypass line and flow-sensing devices, minimum flow through the chiller can be maintained by three-way valves. (Use enough three-way valves to assure that the minimum evaporator-flow rate of the chiller is always satisfied.) This simple approach will reduce pumping costs while providing the chiller with enough chilled water.

To quantify the savings potential of variable versus constant primary flow in a single-chiller plant, we examined a two-story office building in St. Louis, Missouri. The HVAC system includes a 50-ton scroll chiller and a 5-hp chilled water pump. Figure 39 illustrates the results of our analysis. Although the absolute savings are not large, variable primary flow did reduce the cost of operating the chilled water system by more than 6 percent … enough to warrant further investigation. The difference in installed costs is a variable- speed drive, a differential pressure sensor, and a pump controller.

SYS-APM001-EN

Chiller System Design and Control

67

Image 73
Contents May Page Chiller System Design and Control Preface Contents 100 Chiller Primary System ComponentsChiller evaporator Primary System ComponentsEffect of chilled-water flow rate and variation Effect of chilled-water temperatureWater-cooled condenser Effect of condenser-water temperatureEffect of condenser-water flow rate Air-cooled condenser MaintenanceAir-cooled versus water-cooled condensers Packaged or Split System?Energy efficiency Low-ambient operationAir-cooled or water-cooled efficiency LoadsTwo-way valve load control Three-way valve load controlFace-and-bypass dampers Variable-speed pump load controlChilled-water pump Chilled-Water Distribution SystemPump per chiller Distribution pipingManifolded pumps Constant flow system Pumping arrangementsCooling tower Condenser-Water SystemPrimary-secondary system Variable-primary systemEffect of load on cooling tower performance Condenser-water pumping arrangementsEffect of ambient conditions on cooling tower performance Single tower per chillerChiller control Unit-Level ControlsRecommended chiller-monitoring points per Ashrae Standard Centrifugal chiller with AFD Centrifugal chiller capacity controlAFD on both chillers Small Chilled-Water Systems 1-2 chillers Application ConsiderationsVariable flow Application Considerations Constant flowCondensing method Number of chillers Application ConsiderationsParallel or series Part load system operationManaging control complexity Mid-Sized Chilled-Water Systems ChillersPreferential vs. equalized loading and run-time Large Chilled-Water Systems + Chillers, District Cooling Large chilled-water system schematicPipe size PowerWater Limitations of field performance testing Chiller performance testingChiller Plant System Performance ControlsSYS-APM001-EN SYS-APM001-EN Guidance for Chilled- and Condenser-Water Flow Rates System Design OptionsStandard rating temperatures Chilled-Water TemperaturesSystem Design Options Chilled- and Condenser-Water Flow Rates Condenser-Water TemperaturesStandard rating flow conditions System Design Options Selecting flow rates Low-flow conditions for cooling tower Base Case Low Flow DP2/DP1 = Flow2/Flow11.85System summary at full load Total system power Component Power kW Base Case Low FlowChilled water system performance at part load Coil response to decreased entering water temperatureCooling-tower options with low flow Entering fluid temperature, F CSmaller tower System designSame tower, smaller approach ΔT2 = 99.1 78 = 21.1F or 37.3 25.6 = 11.7CSame tower, smaller approach Present Smaller Approach Same tower, larger chillerRetrofit capacity changes Larger Present Chiller Same tower Retrofit opportunitiesCost Implications Misconception 1-Low flow is only good for long piping runs Misconceptions about Low-Flow RatesKWh SYS-APM001-EN Parallel Chillers System ConfigurationsParallel chillers with separate, dedicated chiller pumps System ConfigurationsSeries chillers Series ChillersHydraulic decoupling Primary-Secondary Decoupled SystemsCheck valves Production loop System Configurations ProductionDistribution-loop benefits of decoupled system arrangement System Configurations DistributionCampus CommonTertiary or distributed Tertiary pumping arrangement Decoupled system-principle of operationFlow-based control Temperature-sensingFlow-sensing Adding a chiller Multiple chilled-water plants on a distribution loopSubtracting a chiller Double-ended decoupled system Pump control in a double-ended decoupled systemChiller sequencing in a double-ended decoupled system Other plant designs Variable-Primary-Flow SystemsOperational savings of VPF designs Advantages of variable primary flowDispelling a common misconception Chiller selection requirementsFlow, ft.water Flow rate Flow-rate changes that result from isolation-valve operation Managing transient water flowsSystem Configurations Effect of dissimilar evaporator pressure drops System design and control requirementsAccurate flow measurement Bypass flow control Chiller sequencing in VPF systems Flow-rate-fluctuation examples Adding a chiller in a VPF systemSequencing based on load Subtracting a chiller in a VPF systemSelect slow-acting valves to control the airside coils Other VPF control considerationsConsider a series arrangement for small VPF applications Plant configurationChiller selection Guidelines for a successful VPF systemBypass flow Plant configurationChiller sequencing Airside controlChilled-Water System Variations Heat RecoveryCondenser Free Cooling or Water Economizer Plate-and-frame heat exchangerRefrigerant migration Chilled-Water System VariationsWell, river, or lake water Refrigerant migration chiller in free-cooling modePreferential loading parallel arrangement Preferential LoadingSidestream plate-and-frame heat exchanger Preferential loading sidestream arrangementChilled-Water System Variations Sidestream with alternative fuels or absorptionSidestream system control Preferential loading series arrangementSeries-series counterflow Series-Counterflow ApplicationEvaporators Unequal Chiller SizingCondensers Low ΔT Syndrome System Issues and ChallengesAmount of Fluid in the Loop Chiller response to changing conditions System Issues and ChallengesSystem response to changing conditions ExampleMinimum capacity required ContingencyType and size of chiller Alternative Energy Sources System Issues and Challenges Location of equipmentWater and electrical connections Ancillary equipmentAlternative fuel Plant ExpansionThermal storage Applications Outside the Chiller’s Range Retrofit OpportunitiesFlow rate out of range Precise temperature control System Issues and Challenges Temperatures out of rangePrecise temperature control, multiple chillers System Controls Chilled water reset-raising and loweringChilled-Water System Control Chilled-water pump controlSystem Controls Critical valve reset pump pressure optimizationNumber of chillers to operate Minimum refrigerant pressure differential Condenser-Water System ControlVFDs and centrifugal chillers performance at 90% load Chillers DifferenceCooling-tower-fan control Condenser-water temperature controlChiller-tower energy consumption Chiller-tower energy balanceChiller-tower-pump balance System Controls Variable condenser water flowEffect of chiller load on water pumps and cooling tower fans Decoupled condenser-water systemCDWP-2 Failure recovery Failure RecoveryConclusion Glossary Pumps system GlossaryGlossary Plant. Idea 88th Annual Conference Proceedings 1997 ReferencesEngineering July References102 Ashrae IndexIndex 105 106 Page Trane