Primary System Components
by reducing motor speed at “low-lift” conditions, when cooler condenser water is available.
Certain system characteristics favor the application of an AFD, including:
•A substantial number of part-load operating hours (for example, when an air- or water-economizer is not installed in the system)
•The availability of cooler condenser water (condenser-water reset)
•Chilled-water reset control
Chiller savings using condenser- and chilled-water-temperature reset, however, should be balanced against the increase in pumping and cooling- tower energy. Performing a comprehensive energy analysis is the best method of determining whether an AFD is desirable. It is important to use actual utility costs, not a “combined” cost, for demand and consumption charges. It is also important to include drive maintenance and replacement costs, since the drive life is shorter than the chiller life. See “Energy and economic analysis of alternatives” on page 26.
Depending on the application, it may make sense to use the additional money that would be needed to purchase an AFD to purchase a more efficient chiller instead. This is especially true if demand charges are significant, or if the condenser water is close to its design temperature most of the time (e.g., in a hot and humid climate such as Miami).
Consider the following analysis of an 800-ton office building with two chillers. The analysis compares equally priced high efficiency or AFD- equipped chillers, as one or both of the chillers. Utility costs for the combined or “blended” rate are $0.10 per kWh and for the actual rate are $12 per kW and $0.06 per kWh.
Simple paybacks using the combined rate analysis show almost no difference between the two options (Table 2). However, when utility costs with an actual consumption and demand component are used, the difference between the alternatives is much more pronounced. The conclusion is that using actual energy rates matters a great deal.
Table 2. Analysis of high-efficiency chiller options with combined vs actual rates
Simple paybacks, humid climate | Combined rate | Actual rate |
| | |
AFD on both chillers | 7.2 | 12.7 |
| | |
High efficiency on both chillers | 7.1 | 8.3 |
| | |
AFD on one chiller | 6.1 | 10.8 |
| | |
High efficiency on one chiller | 6.3 | 7.7 |
| | |
SYS-APM001-EN | Chiller System Design and Control | 17 |
Contents
May
Page
Chiller System Design and Control
Preface
Contents
100
Chiller
Primary System Components
Chiller evaporator
Primary System Components
Effect of chilled-water flow rate and variation
Effect of chilled-water temperature
Effect of condenser-water flow rate
Effect of condenser-water temperature
Water-cooled condenser
Packaged or Split System?
Maintenance
Air-cooled condenser
Air-cooled versus water-cooled condensers
Energy efficiency
Low-ambient operation
Air-cooled or water-cooled efficiency
Loads
Two-way valve load control
Three-way valve load control
Face-and-bypass dampers
Variable-speed pump load control
Chilled-water pump
Chilled-Water Distribution System
Manifolded pumps
Distribution piping
Pump per chiller
Constant flow system
Pumping arrangements
Variable-primary system
Condenser-Water System
Cooling tower
Primary-secondary system
Single tower per chiller
Condenser-water pumping arrangements
Effect of load on cooling tower performance
Effect of ambient conditions on cooling tower performance
Recommended chiller-monitoring points per Ashrae Standard
Unit-Level Controls
Chiller control
Centrifugal chiller with AFD
Centrifugal chiller capacity control
AFD on both chillers
Small Chilled-Water Systems 1-2 chillers
Application Considerations
Condensing method
Application Considerations Constant flow
Variable flow
Part load system operation
Application Considerations
Number of chillers
Parallel or series
Preferential vs. equalized loading and run-time
Mid-Sized Chilled-Water Systems Chillers
Managing control complexity
Large Chilled-Water Systems + Chillers, District Cooling
Large chilled-water system schematic
Water
Power
Pipe size
Controls
Chiller performance testing
Limitations of field performance testing
Chiller Plant System Performance
SYS-APM001-EN
SYS-APM001-EN
Guidance for Chilled- and Condenser-Water Flow Rates
System Design Options
System Design Options
Chilled-Water Temperatures
Standard rating temperatures
Standard rating flow conditions
Condenser-Water Temperatures
Chilled- and Condenser-Water Flow Rates
System Design Options Selecting flow rates
Low-flow conditions for cooling tower Base Case Low Flow
DP2/DP1 = Flow2/Flow11.85
System summary at full load
Total system power Component Power kW Base Case Low Flow
Chilled water system performance at part load
Coil response to decreased entering water temperature
System design
Entering fluid temperature, F C
Cooling-tower options with low flow
Smaller tower
Same tower, smaller approach
ΔT2 = 99.1 78 = 21.1F or 37.3 25.6 = 11.7C
Same tower, smaller approach Present Smaller Approach
Same tower, larger chiller
Retrofit capacity changes Larger Present Chiller Same tower
Retrofit opportunities
Cost Implications
Misconception 1-Low flow is only good for long piping runs
Misconceptions about Low-Flow Rates
KWh
SYS-APM001-EN
Parallel Chillers
System Configurations
Parallel chillers with separate, dedicated chiller pumps
System Configurations
Series chillers
Series Chillers
Hydraulic decoupling
Primary-Secondary Decoupled Systems
Check valves
Production loop
System Configurations Production
Distribution-loop benefits of decoupled system arrangement
System Configurations Distribution
Tertiary or distributed
Common
Campus
Tertiary pumping arrangement
Decoupled system-principle of operation
Flow-sensing
Temperature-sensing
Flow-based control
Subtracting a chiller
Multiple chilled-water plants on a distribution loop
Adding a chiller
Double-ended decoupled system
Pump control in a double-ended decoupled system
Chiller sequencing in a double-ended decoupled system
Other plant designs
Variable-Primary-Flow Systems
Operational savings of VPF designs
Advantages of variable primary flow
Dispelling a common misconception
Chiller selection requirements
Flow, ft.water Flow rate
Flow-rate changes that result from isolation-valve operation
Managing transient water flows
System Configurations
Effect of dissimilar evaporator pressure drops
System design and control requirements
Accurate flow measurement
Bypass flow control
Chiller sequencing in VPF systems
Flow-rate-fluctuation examples
Adding a chiller in a VPF system
Sequencing based on load
Subtracting a chiller in a VPF system
Select slow-acting valves to control the airside coils
Other VPF control considerations
Consider a series arrangement for small VPF applications
Plant configuration
Chiller selection
Guidelines for a successful VPF system
Airside control
Plant configuration
Bypass flow
Chiller sequencing
Plate-and-frame heat exchanger
Heat Recovery
Chilled-Water System Variations
Condenser Free Cooling or Water Economizer
Refrigerant migration
Chilled-Water System Variations
Well, river, or lake water
Refrigerant migration chiller in free-cooling mode
Preferential loading parallel arrangement
Preferential Loading
Sidestream plate-and-frame heat exchanger
Preferential loading sidestream arrangement
Chilled-Water System Variations
Sidestream with alternative fuels or absorption
Sidestream system control
Preferential loading series arrangement
Series-series counterflow
Series-Counterflow Application
Condensers
Unequal Chiller Sizing
Evaporators
Amount of Fluid in the Loop
System Issues and Challenges
Low ΔT Syndrome
Example
System Issues and Challenges
Chiller response to changing conditions
System response to changing conditions
Type and size of chiller
Contingency
Minimum capacity required
Ancillary equipment
System Issues and Challenges Location of equipment
Alternative Energy Sources
Water and electrical connections
Thermal storage
Plant Expansion
Alternative fuel
Flow rate out of range
Retrofit Opportunities
Applications Outside the Chiller’s Range
Precise temperature control
System Issues and Challenges Temperatures out of range
Precise temperature control, multiple chillers
Chilled-water pump control
Chilled water reset-raising and lowering
System Controls
Chilled-Water System Control
Number of chillers to operate
Critical valve reset pump pressure optimization
System Controls
Chillers Difference
Condenser-Water System Control
Minimum refrigerant pressure differential
VFDs and centrifugal chillers performance at 90% load
Cooling-tower-fan control
Condenser-water temperature control
Chiller-tower energy consumption
Chiller-tower energy balance
Chiller-tower-pump balance
System Controls Variable condenser water flow
Effect of chiller load on water pumps and cooling tower fans
Decoupled condenser-water system
CDWP-2
Failure recovery
Failure Recovery
Conclusion