Trane SYS-APM001-EN manual System Issues and Challenges Temperatures out of range

Page 91

System Issues and Challenges

Temperatures out of range

A laboratory load requires 120 gpm [7.6 L/s] of water entering the process at 85°F [29.4°C] and returning at 95°F [35°C]. The accuracy required is more precise than the cooling tower can provide. The selected chiller has adequate capacity, but a maximum leaving-chilled-water temperature of 60°F [15.6°C].

Using a pair of bypass pipes allows the mixing valve to supply the proper temperature to the process load and maintains acceptable water flow rates and temperatures through the chiller. In the example shown in Figure 52, the chiller and process flow rates are equal, although this is not a requirement. For example, if the chiller had a higher flow rate, more water would bypass and mix with the warm return water.

Figure 52. Temperatures out of range for equipment

 

 

60°F [15.6°C]

60°F [15.6°C]

35 gpm [2.2 L/s]

120 gpm

 

 

 

[7.6 L/s]

 

 

Mixing

 

 

60°F [15.6°C]

 

 

Valve

 

 

85 gpm

 

 

 

[5.4 L/s]

 

Chiller

70°F [21.1°C]

Bypass

Pipes

 

120 gpm

 

 

 

[7.6 L/s]

 

85°F [29.4°C]

120 gpm [7.6 L/s]

Constant Volume

Pump

95°F [35°C]

Process

85 gpm [5.4 L/s]

Load

Constant Volume

95°F [35°C]

95°F [35°C]

Pump

35 gpm [2 .2 L/s]

120 gpm [7.6 L/s]

120gpm [7.6 L/s]

 

 

Precise temperature control

An example of a process application layout where the required temperature control tolerance is more precise than the chiller controls allow is shown in Figure 53.

For example, when Chiller 2 is turned on, it takes a certain amount of time to reach its supply-temperature setpoint. The dedicated control valve remains closed and water is bypassed until Chiller 2 reaches its setpoint, which keeps the water temperature supplied to the process within tolerance. When Chiller 2 reaches its setpoint, the control valve opens.

This design requires a different chiller-sequencing strategy than the standard decoupled system. Water must not be allowed to bypass from the return side to the supply side, since this will cause the temperature of the water supplied to the process to vary outside the tolerance. Set the system controls to turn on Chiller 2 before deficit flow occurs.

SYS-APM001-EN

Chiller System Design and Control

85

Image 91
Contents May Page Chiller System Design and Control Preface Contents 100 Chiller Primary System ComponentsChiller evaporator Primary System ComponentsEffect of chilled-water flow rate and variation Effect of chilled-water temperatureWater-cooled condenser Effect of condenser-water temperatureEffect of condenser-water flow rate Packaged or Split System? MaintenanceAir-cooled condenser Air-cooled versus water-cooled condensersEnergy efficiency Low-ambient operationAir-cooled or water-cooled efficiency LoadsTwo-way valve load control Three-way valve load controlFace-and-bypass dampers Variable-speed pump load controlChilled-water pump Chilled-Water Distribution SystemPump per chiller Distribution pipingManifolded pumps Constant flow system Pumping arrangementsVariable-primary system Condenser-Water SystemCooling tower Primary-secondary systemSingle tower per chiller Condenser-water pumping arrangementsEffect of load on cooling tower performance Effect of ambient conditions on cooling tower performanceChiller control Unit-Level ControlsRecommended chiller-monitoring points per Ashrae Standard Centrifugal chiller with AFD Centrifugal chiller capacity controlAFD on both chillers Small Chilled-Water Systems 1-2 chillers Application ConsiderationsVariable flow Application Considerations Constant flowCondensing method Part load system operation Application ConsiderationsNumber of chillers Parallel or seriesManaging control complexity Mid-Sized Chilled-Water Systems ChillersPreferential vs. equalized loading and run-time Large Chilled-Water Systems + Chillers, District Cooling Large chilled-water system schematicPipe size PowerWater Controls Chiller performance testingLimitations of field performance testing Chiller Plant System PerformanceSYS-APM001-EN SYS-APM001-EN Guidance for Chilled- and Condenser-Water Flow Rates System Design OptionsStandard rating temperatures Chilled-Water TemperaturesSystem Design Options Chilled- and Condenser-Water Flow Rates Condenser-Water TemperaturesStandard rating flow conditions System Design Options Selecting flow rates Low-flow conditions for cooling tower Base Case Low Flow DP2/DP1 = Flow2/Flow11.85System summary at full load Total system power Component Power kW Base Case Low FlowChilled water system performance at part load Coil response to decreased entering water temperatureSystem design Entering fluid temperature, F CCooling-tower options with low flow Smaller towerSame tower, smaller approach ΔT2 = 99.1 78 = 21.1F or 37.3 25.6 = 11.7CSame tower, smaller approach Present Smaller Approach Same tower, larger chillerRetrofit capacity changes Larger Present Chiller Same tower Retrofit opportunitiesCost Implications Misconception 1-Low flow is only good for long piping runs Misconceptions about Low-Flow RatesKWh SYS-APM001-EN Parallel Chillers System ConfigurationsParallel chillers with separate, dedicated chiller pumps System ConfigurationsSeries chillers Series ChillersHydraulic decoupling Primary-Secondary Decoupled SystemsCheck valves Production loop System Configurations ProductionDistribution-loop benefits of decoupled system arrangement System Configurations DistributionCampus CommonTertiary or distributed Tertiary pumping arrangement Decoupled system-principle of operationFlow-based control Temperature-sensingFlow-sensing Adding a chiller Multiple chilled-water plants on a distribution loopSubtracting a chiller Double-ended decoupled system Pump control in a double-ended decoupled systemChiller sequencing in a double-ended decoupled system Other plant designs Variable-Primary-Flow SystemsOperational savings of VPF designs Advantages of variable primary flowDispelling a common misconception Chiller selection requirementsFlow, ft.water Flow rate Flow-rate changes that result from isolation-valve operation Managing transient water flowsSystem Configurations Effect of dissimilar evaporator pressure drops System design and control requirementsAccurate flow measurement Bypass flow control Chiller sequencing in VPF systemsFlow-rate-fluctuation examples Adding a chiller in a VPF systemSequencing based on load Subtracting a chiller in a VPF systemSelect slow-acting valves to control the airside coils Other VPF control considerationsConsider a series arrangement for small VPF applications Plant configurationChiller selection Guidelines for a successful VPF systemAirside control Plant configurationBypass flow Chiller sequencingPlate-and-frame heat exchanger Heat RecoveryChilled-Water System Variations Condenser Free Cooling or Water EconomizerRefrigerant migration Chilled-Water System VariationsWell, river, or lake water Refrigerant migration chiller in free-cooling modePreferential loading parallel arrangement Preferential LoadingSidestream plate-and-frame heat exchanger Preferential loading sidestream arrangementChilled-Water System Variations Sidestream with alternative fuels or absorptionSidestream system control Preferential loading series arrangementSeries-series counterflow Series-Counterflow ApplicationEvaporators Unequal Chiller SizingCondensers Low ΔT Syndrome System Issues and ChallengesAmount of Fluid in the Loop Example System Issues and ChallengesChiller response to changing conditions System response to changing conditionsMinimum capacity required ContingencyType and size of chiller Ancillary equipment System Issues and Challenges Location of equipmentAlternative Energy Sources Water and electrical connectionsAlternative fuel Plant ExpansionThermal storage Applications Outside the Chiller’s Range Retrofit OpportunitiesFlow rate out of range Precise temperature control System Issues and Challenges Temperatures out of rangePrecise temperature control, multiple chillers Chilled-water pump control Chilled water reset-raising and loweringSystem Controls Chilled-Water System ControlSystem Controls Critical valve reset pump pressure optimizationNumber of chillers to operate Chillers Difference Condenser-Water System ControlMinimum refrigerant pressure differential VFDs and centrifugal chillers performance at 90% loadCooling-tower-fan control Condenser-water temperature controlChiller-tower energy consumption Chiller-tower energy balanceChiller-tower-pump balance System Controls Variable condenser water flowEffect of chiller load on water pumps and cooling tower fans Decoupled condenser-water systemCDWP-2 Failure recovery Failure RecoveryConclusion Glossary Pumps system GlossaryGlossary Plant. Idea 88th Annual Conference Proceedings 1997 ReferencesEngineering July References102 Ashrae IndexIndex 105 106 Page Trane

SYS-APM001-EN specifications

The Trane SYS-APM001-EN is an advanced control system designed for HVAC (Heating, Ventilation, and Air Conditioning) applications, specifically tailored to enhance energy efficiency and system performance. This comprehensive solution integrates cutting-edge technologies to optimize climate control in commercial and industrial environments.

One of the main features of the SYS-APM001-EN is its intuitive user interface. The system is equipped with a large, easy-to-read display that provides real-time data on system performance, energy usage, and environmental conditions. This user-friendly interface makes it simple for operators to monitor and adjust settings, ensuring optimal comfort levels and efficient energy consumption.

Another key characteristic of the SYS-APM001-EN is its advanced data analytics capabilities. The system collects and analyzes data from various sensors throughout the building, providing insights into occupancy patterns, equipment performance, and energy consumption trends. This data-driven approach allows facility managers to make informed decisions about system adjustments, predictive maintenance, and energy savings.

The SYS-APM001-EN also boasts robust integration capabilities. It can seamlessly connect with a variety of building management systems (BMS) and other third-party devices. This interoperability enables a cohesive operational ecosystem where HVAC systems can communicate and cooperate with lighting, security, and fire safety systems, enhancing overall building efficiency.

Energy efficiency is a hallmark of the SYS-APM001-EN, as it implements sophisticated algorithms to optimize system operation. These algorithms adjust equipment performance in real-time based on current conditions, thereby reducing energy waste and lowering operational costs. The system is designed to support multiple energy-saving strategies, including demand-controlled ventilation and optimal start/stop scheduling.

Additionally, the SYS-APM001-EN is built with scalability in mind, accommodating facilities of various sizes and configurations. Whether it’s a small office building or a large industrial complex, the system can be tailored to meet specific needs, ensuring that HVAC performance aligns with operational goals.

In conclusion, the Trane SYS-APM001-EN is an innovative HVAC control solution that emphasizes user experience, data-driven decision-making, and energy efficiency. With its advanced features and technologies, it is an essential tool for optimizing building performance and enhancing occupant comfort while reducing environmental impact.