6.0SERVICE
WARNING: Disconnect unit from power supply before cleaning or servicing appliance.
GENERAL
When any difficulty arises always check that the unit has been connected to the gas supply type and voltage for which it was supplied. This can be done by examining the serial plate on the lower right side of the unit. It will list the gas type and voltage for which the unit was manufactured.
Wiring diagrams for the unit are located in a small envelope affixed to the rear side of the front control panel.
|
| Orifice Size | |
Unit | Total Input | Natural | Propane |
100,000 BTU/Hour | 29 | 44 | |
100,000 BTU/Hour | 29 | 44 | |
|
|
|
|
130,000 BTU/Hour | 23 | 39 |
MANIFOLD PRESSURE
Natural Gas - 4 inches W.C.
PILOTS
LP Gas - 10 inches W.C.
The pilot adjustment is part of the combination control valve located just behind the lower front access door. It is located on the centre left side of the control just below the large slotted screw head. (See Figure 1). Remove the large slotted screw; below this is a second slotted screw used for adjustment of the pilot burner flame.
Figure 1
Top view of gas control