Installation Instructions

COMPLETE PIPING CONNECTIONS

8.Charge to proper weight, charge based on feet of interconnect (tables starting on page 10).

9.Refer to Charts on page 12 to “fine tune” the refrigerant charge to meet your conditions.

S1C

S2C

Shown

Shown

Note: Charging should be done with a dial-a-charge or weighed in with a scale.

REFRIGERANT PROCESSING

IMPORTANT NOTES:

1. To find the charge adjustment and system charge for any evaporator and tubing length:

Line Adjustment = (Line Charge/FT) x Line Length

System Total = Factory Charge + Line Adjustment 2. Round to the nearest ounce and allow for gauges and hoses.

S1C REFRIGERANT CHARGE TABLE

CONDENSER

 

EVAPORATOR PAIRING

LINE CHG/FT

FACTORY CHARGE

S1C9

 

CAH12

.25 oz.

37 oz.

S1C2

 

CAH12

.25 oz.

40 oz.

S1C8

 

CAH24

.56 oz.

51 oz.

S1C4

 

CAH24

.56 oz.

65 oz.

S1C3

 

CAC36

.56 oz.

72 oz.

S1C6

 

CAC36

.56 oz.

90 oz.

S1C9

 

WLH09/UNH09

.25 oz.

37 oz.

S1C2

 

WLH12/UNH12

.25 oz.

40 oz.

S1C8

 

WLH24/UNH24

.56 oz.

51 oz.

S1C4

 

WLH24/UNH24

.56 oz.

65 oz.

 

 

 

 

 

S1C3

 

WLC30/UNC36

.56 oz.

72 oz.

 

 

 

 

 

S1C6

 

WLC36/UNC36

.56 oz.

90 oz.

 

 

 

 

 

 

S1H (Heat Pump) REFRIGERANT CHARGE TABLE

CONDENSER

 

EVAPORATOR PAIRING

LINE CHG/FT

FACTORY CHARGE

S1H9

 

WLH09/UNH09

.25 oz.

41 oz.

S1H2

 

WLH12/UNH12

.25 oz.

44 oz.

S1H8

 

WLH24/UNH24

.56 oz.

53 oz.

S1H4

 

WLH24/UNH24

.56 oz.

67 oz.

Side Discharge Condensers

10

www.enviromaster.com

Image 10
Contents Installation, operation and maintenance Manual Installation, operation and maintenance Manual S1C/S1H Single-Zone & S2C Dual-Zone Condensing UnitsControls and Components System OPTIOnsInstallation Instructions Items for ConsiderationS1C High Volt Connection Completed Electrical ConnectionsRefrigerant Piping Installation Instructions Trap Installation Clean the ends of tubing and insert into fittings Refrigerant Processing Installation Instructions Refrigerant Processing S2C Refrigerant Charge TableSingle Zone Operation Charts Single Zone Operation Charts Single Zone Operation Charts Single Zone Operation Charts Single Zone Heat Pump Operation Charts Single Zone Heat Pump Operation Charts Dual Zone Operation Charts Preperation for Start-Up Single-Zone and Dual-Zone Condenser Sequence of OperationFactory settings 9-24k Btu = 90 minutesW Single-Zone and Dual-Zone Sequence of OperationDefrost Control Board S1C/S1H Specifications and dimensions S2c specifications and dimensionsS1C Electrical Specifications S1H Electrical Specifications S2c Test Unit Performance Data sheet Test Unit Performance DataEMI’s Product Line Phone Success Drive Fax Rome, NY