EMI Volts/HZ/pH manual Installation Instructions Trap Installation

Page 8

Installation Instructions

P-Trap Installation

A P-trap is recommended when the suc- tion riser is equal to or greater than 20 feet in height.

When the condenser is installed above the evaporator, the P-trap will help the return of oil back to the compressor.

The placement of the P-trap should be at the halfway mark of the suction riser. For example if the suction riser is 30 feet tall then a P-trap is recommended at the 15 foot mark of the suction riser (see

Figure 1).

A P-trap may be fabricated using (2) street elbows and (2) regular elbow. A prefab-

ricated trap may be purchased from a wholesaler or distributor however the trap should be shallow as the (3) elbow con- figuration. Each elbow is approximately 2 equivalent feet. One P-trap is equal to approximately 12 equivalent feet.

NOTE: Avoid excessive oil buildup. The P-trap should have a shallow depth and a short horizontal section.

P-traps are not required at the foot of the hot gas risers due to increased oil flow at higher temperatures.

Figure 1

Condenser

30'

15'

Evaporator

Side Discharge Condensers

8

www.enviromaster.com

Image 8
Contents Installation, operation and maintenance Manual Installation, operation and maintenance Manual S1C/S1H Single-Zone & S2C Dual-Zone Condensing UnitsControls and Components System OPTIOnsInstallation Instructions Items for ConsiderationS1C High Volt Connection Completed Electrical ConnectionsRefrigerant Piping Installation Instructions Trap Installation Clean the ends of tubing and insert into fittings Refrigerant Processing Installation Instructions Refrigerant Processing S2C Refrigerant Charge TableSingle Zone Operation Charts Single Zone Operation Charts Single Zone Operation Charts Single Zone Operation Charts Single Zone Heat Pump Operation Charts Single Zone Heat Pump Operation Charts Dual Zone Operation Charts Preperation for Start-Up Single-Zone and Dual-Zone Condenser Sequence of OperationFactory settings 9-24k Btu = 90 minutesW Single-Zone and Dual-Zone Sequence of OperationDefrost Control Board S1C/S1H Specifications and dimensions S2c specifications and dimensionsS1C Electrical Specifications S1H Electrical Specifications S2c Test Unit Performance Data sheet Test Unit Performance DataEMI’s Product Line Phone Success Drive Fax Rome, NY