EMI Volts/HZ/pH manual Clean the ends of tubing and insert into fittings

Page 9

Installation Instructions

REFRIGERANT PIPING

Continued

1.Clean the ends of tubing and insert into fittings.

S2C

S1C

Shown

S1C

Shown

5. Attach manifold set.

manifold

Vaccum Pump Micron Gage

2.Protect the valves by wrapping with a wet rag "heat sink" before brazing.

S1C

Shown

3.We recommend the use of a shield (can be made from some scrap metal) to protect the paint.

S1C

Shown

Manifold Setup For Evacuation

6.Evacuate line to 500 microns or less to ensure all moisture has been removed and there are no leaks.

 

S1C

 

Shown

 

Refer to Refrigerant

 

Charge Table for

 

specified line charge.

S2C

7. Once certain of a good evacuation and

Shown

 

leak free joints, back-seat the valves

 

(counter-clockwise) to open and allow

4. Braze tubing into fittings.

factory charge to fill lines and indoor unit.

Side Discharge Condensers

9

www.enviromaster.com

Image 9
Contents Installation, operation and maintenance Manual S1C/S1H Single-Zone & S2C Dual-Zone Condensing Units Installation, operation and maintenance ManualSystem OPTIOns Controls and ComponentsItems for Consideration Installation InstructionsS1C Completed Electrical Connections High Volt ConnectionRefrigerant Piping Installation Instructions Trap Installation Clean the ends of tubing and insert into fittings Refrigerant Processing S2C Refrigerant Charge Table Installation Instructions Refrigerant ProcessingSingle Zone Operation Charts Single Zone Operation Charts Single Zone Operation Charts Single Zone Operation Charts Single Zone Heat Pump Operation Charts Single Zone Heat Pump Operation Charts Dual Zone Operation Charts Single-Zone and Dual-Zone Condenser Sequence of Operation Preperation for Start-UpSingle-Zone and Dual-Zone Sequence of Operation Factory settings 9-24k Btu = 90 minutesWDefrost Control Board S2c specifications and dimensions S1C/S1H Specifications and dimensionsS1C Electrical Specifications S1H Electrical Specifications S2c Test Unit Performance Data Test Unit Performance Data sheetEMI’s Product Line Phone Success Drive Fax Rome, NY