EMI Volts/HZ/pH Installation Instructions Refrigerant Processing, S2C Refrigerant Charge Table

Page 11

Installation Instructions

REFRIGERANT PROCESSING continued

S2C REFRIGERANT CHARGE TABLE

CONDENSER

EVAPORATOR PAIRING

LINE CHG/FT

FACTORY CHARGE

S2C99

WLH09

.25 oz.

28 oz./ 28 oz.

S2C22

WLH12

.25 oz.

33 oz./ 33 oz.

S2C92

WLH09+WLH12

.25 oz.

28 oz./ 33 oz.

S2C99

CAC12

.25 oz.

28 oz./ 28 oz.

S2C22

CAC12

.25 oz.

33 oz./ 33 oz.

S2C92

CAC12

.25 oz.

28 oz./ 33 oz.

S2C99

UNH09

.25 oz.

28 oz./ 28 oz.

S2C22

UNH12

.25 oz.

33 oz./ 33 oz.

S2C92

UNH09+UNH12

.25 oz.

28 oz./ 33 oz.

WARNING

It is illegal to discharge refrigerant into the atmosphere. Use proper re- claiming methods & equipment when installing or servicing this unit.

The units are delivered precharged with refrigerant for the condenser coil and the evaporator. Charging of the field installed piping is required. Refer to the refrigerant charge table for the proper amount to be added for the applications interconect piping. Unit service valves are solid brass, for sweat connections.

IMPORTANT: All systems require field charge adjustments. Refer to the "Refrigerant Charge Tables" for proper weight charge and to the supplied "Operational Charts" for proper system pressures and temperature at different outdoor conditions. Superheat should be used for final system charge.

When charging and checking pres- sures/temperatures on system supplied with Low Ambient Option, the fan cycle switch should be jumped out of the circuit temporarily to obtain accurate data.

Note: The following air handlers are equivelent in electrical specifications and system combinations.

WLH09 = UNH09

WLH12 = WLH12

WLH24 = UNH24

WLC30 = UNC36

WLC36 = UNC36

Side Discharge Condensers

11

www.enviromaster.com

Image 11
Contents Installation, operation and maintenance Manual S1C/S1H Single-Zone & S2C Dual-Zone Condensing Units Installation, operation and maintenance ManualSystem OPTIOns Controls and ComponentsItems for Consideration Installation InstructionsS1C Completed Electrical Connections High Volt ConnectionRefrigerant Piping Installation Instructions Trap Installation Clean the ends of tubing and insert into fittings Refrigerant Processing S2C Refrigerant Charge Table Installation Instructions Refrigerant ProcessingSingle Zone Operation Charts Single Zone Operation Charts Single Zone Operation Charts Single Zone Operation Charts Single Zone Heat Pump Operation Charts Single Zone Heat Pump Operation Charts Dual Zone Operation Charts Single-Zone and Dual-Zone Condenser Sequence of Operation Preperation for Start-UpSingle-Zone and Dual-Zone Sequence of Operation Factory settings 9-24k Btu = 90 minutesWDefrost Control Board S2c specifications and dimensions S1C/S1H Specifications and dimensionsS1C Electrical Specifications S1H Electrical Specifications S2c Test Unit Performance Data Test Unit Performance Data sheetEMI’s Product Line Phone Success Drive Fax Rome, NY