EMI Volts/HZ/pH manual S1C Electrical Specifications

Page 23

S1C/S1H Specifications and dimensions

NOTE: All EMI products are subject to ongoing development. Design and specifications may

change without notice.

S1C Electrical Specifications

Model #

Volts/HZ/PH

Fan Motor

Compressor

Total

Min

M.C.A.

HACR

AMPS

HP

RLA

LRA

AMPS

Volt

BRKR

 

 

 

 

 

 

 

 

 

S1C9A

115/60/1

1.4

0.125

6.7

29.0

8.1

104

9.8

15

S1C2A

115/60/1

1.4

0.125

8.4

44.0

9.8

104

11.9

20

S1C9D

208/230/60/1

0.8

0.125

3.5

19.0

4.3

197

5.2

15

S1C2D

208/230/60/1

0.8

0.125

4.5

21.0

5.3

197

6.4

15

 

 

 

 

 

 

 

 

 

 

S1C8D

208/230/60/1

0.8

0.125

5.4

36.0

6.2

197

7.6

15

 

 

 

 

 

 

 

 

 

 

S1C4D

208/230/60/1

0.8

0.125

8.0

53.5

8.8

197

10.8

15

 

 

 

 

 

 

 

 

 

 

S1C3D

208/230/60/1

1.8

0.330

9.8

60.0

11.6

197

14.1

20

S1C6D

208/230/60/1

1.8

0.330

11.8

78.0

13.6

197

16.6

25

System Performance Data: Matched with EMI AmericaSeries indoor units

Cooling Systems with Wall Units

Condenser

Wall Unit

Btuh

SEER

SHR

EER

Ref.

S1C9

WLH09

9,000

13.0

.79

11.8

R22

S1C2

WLH12

12,000

13.0

.74

12.9

R22

* S1C8

WLH24

18,000

14.0

.78

13.0

R22

S1C4

WLH24

24,000

13.0

.70

12.5

R22

S1C3

WLC30

30,000

13.0

.72

12.6

R22

S1C6

WLC36

33,600

13.0

.69

12.1

R22

Cooling Systems with Cassette Units

Condenser

Cassette

Btuh

SEER

SHR

EER

Ref.

S1C9

CAH12

9,000

13.0

.79

11.7

R22

S1C2

CAH12

12,000

13.0

.72

12.2

R22

S1C8

CAH24

18,000

13.0

.76

12.3

R22

S1C4

CAH24

23,000

13.0

.67

11.8

R22

* S1C3

CAC36

30,000

14.0

.82

12.0

R22

S1C6

CAC36

36,000

13.0

.74

12.6

R22

 

 

 

 

 

 

 

Cooling Systems with Universal Units

Condenser

Universal

Btuh

SEER

SHR

EER

Ref.

S1C9

UNH09

9,000

13.0

.77

11.6

R22

S1C2

UNH12

11,800

13.0

.76

12.3

R22

S1C8

UNH24

18,000

13.0

.76

12.4

R22

S1C4

UNH24

24,000

13.0

.69

12.0

R22

S1C3

UNC36

28,500

13.0

.71

12.0

R22

S1C6

UNC36

31,000

13.0

.67

12.0

R22

*Important - This system has been designed and manufactured to meet ENERGY STAR criteria for energy efficiency. However, proper refrigerant charge and proper air flow are critical to achieve rated capac-

ity and efficiency. Installation of this product should follow the manufacturer’s refrigerant charging and air flow instructions.

Failure to confirm proper charge and airflow may reduce energy efficiency and shorten equipment life.

WLC/wlh

CAC

UNC/UNH

Side Discharge Condensers

23

www.enviromaster.com

Image 23
Contents Installation, operation and maintenance Manual S1C/S1H Single-Zone & S2C Dual-Zone Condensing Units Installation, operation and maintenance ManualSystem OPTIOns Controls and ComponentsItems for Consideration Installation InstructionsS1C Completed Electrical Connections High Volt ConnectionRefrigerant Piping Installation Instructions Trap Installation Clean the ends of tubing and insert into fittings Refrigerant Processing S2C Refrigerant Charge Table Installation Instructions Refrigerant ProcessingSingle Zone Operation Charts Single Zone Operation Charts Single Zone Operation Charts Single Zone Operation Charts Single Zone Heat Pump Operation Charts Single Zone Heat Pump Operation Charts Dual Zone Operation Charts Single-Zone and Dual-Zone Condenser Sequence of Operation Preperation for Start-UpSingle-Zone and Dual-Zone Sequence of Operation Factory settings 9-24k Btu = 90 minutesWDefrost Control Board S2c specifications and dimensions S1C/S1H Specifications and dimensionsS1C Electrical Specifications S1H Electrical Specifications S2c Test Unit Performance Data Test Unit Performance Data sheetEMI’s Product Line Phone Success Drive Fax Rome, NY