PRODUCT DESCRIPTION
The AmericaSeries S1C/H and S2C condensing units are,
The S1C
The S2C 18,000 (99) - 21,000 (92) and 23,000 (22) Btuh capacity condensing units will provide cooling for two evaporators, as identified on page 25 in the "S2C Specifica- tions and Dimensions" section. The S1C/H and S2C are quiet units that can be recom- mended for both commercial and residential applications.
Installation of the S1C/H and S2C condensing units is simplified by a 24v control interconnection from the evaporator and multiple units can be lined up in close proximity to an exterior wall. Service valves are recessed to reduce tampering and all
ment on other models.
INSTALLER SUPPLIED ITEMS
•Power wiring
•Low volt wiring (18 awg minimum)
•Secure mounting pad or foundation
•Refrigerant piping (if not purchased from EMI)
•High Volt Disconnect
•Refrigerant for charging interconnect piping (see charge table on page 10)
ITEMS FOR CONSIDERATION
CONTROLS and COMPONENTS
(Factory installed or supplied)
•Compressor and fan motor contactor
•Run capacitor
•Loss of charge switch (09 - 12 only)
•Low voltage terminal connections
•Large capacity suction accumulator (09 - 12 only)
•Solid core filter drier (09 - 12 only)
•Thermostatically controlled crankcase heater (09 - 12 S1H’s)
•H.P.S. (High pressure switch)
-Standard on S1H’s (heat pumps)
-Standard on S1C’s 18K and above.
•Low Ambient controls for operation down to 32º F standard, factory in- stalled on all S1H’s (heat pumps)
Thermostatically controlled crankcase heater – This feature energizes the crank- case heater only when needed, removes the heater from the electrical circuit at conditions where it’s not required, saving unnecessary Watts, and increasing overall system efficiency.
System OPTIOns
•Field installed crankcase heater for straight cool units (standard on
•Straight cool hard start (standard on all S1H’s)
•115v
•copper/copper coils (sea coast use)
•Low Ambient controls for operation down to 32º F, specify this option for S1C or S2C systems (standard on S1H’s) that will be operated in cooling mode at outside temperatures below 60º F (field installed kit)
•Low Ambient for operation down to 0º F for S1C, S1H or S2C systems (consult factory for availability)
Low Ambient controls are required when the system is asked to cool at outdoor tem- peratures below 60º F, this may cause dam- age to the compressor and coil, and may
Side Discharge Condensers | 3 | www.enviromaster.com |