EMI Volts/HZ/pH manual Single-Zone and Dual-Zone Sequence of Operation

Page 20

Single-Zone and Dual-Zone Sequence of Operation

Note: For remote wall mounted ther- mostat operation be sure to select EMI p/n 240004180 or a suitable 24v, two sage heating, heat pump thermostat.

Condenser operation: The transform- er located in the indoor unit provides 24V, low-volt control power to the condenser (outdoor unit). This can be measured across low-volt terminals “R” and “C”.

Single zone heat pump condensers utilize a reversing valve to provide re- verse cycle operation. Therefore the out- door unit will act as either a condenser or an evaporator there-by providing comfort cooling or heating to the indoor space. The reversing valve is energized in cool- ing. Should the valve fail to actuate, the system will default to the heating mode of operation.

Cooling operation, single-zone and dual-zone: Cooling operation requires that the control (either unit mount or remote wall mount thermostat) make a connec- tion between low-volt terminals “R” and “Y” along with “R” and “O” (heat pumps only). When the indoor control is placed in cooling mode, with the set point tem- perature below the room temperature, the reversing valve will energize (R & O heat pumps only) along with the compressor and outdoor fan (R & Y). When the indoor control is satisfied and the room tempera- ture falls below the set temperature, the compressor and fan will de-energize. The anti-short cycle timer (ASCT) will prevent the compressor from re-starting for three minutes.

Heating operation (heat pumps only): Heating operation requires that the con- trol (either unit mount or remote wall mount, heat pump thermostat) make a connection between low-Volt terminals “R” and “Y” only. When the indoor control is placed in heating mode, with the set point temperature above room tempera- ture, the compressor and outdoor fan

(R & Y) will energize. When the indoor control is satisfied and the room temper- ature rises above the set temperature, the compressor and fan will de-energize. The anti-short cycle timer (ASCT) will prevent the compressor from re-starting for three minutes.

Defrost controls with short cycle protection (heat pumps only): The unit is equipped with a logic control circuit de- signed to keep system operating at peek efficiency. The 24v circuit provides control to the indoor and outdoor systems includ- ing a three minute, anti-short cycle timer (ASCT) compressor protection.

The defrost control circuit is designed to keep the condenser coil free from frost and ice during heating mode. This is ac- complished through the precise switching sequence of the outdoor fan, reversing valve and indoor auxiliary heater.

Defrost initiation: The defrost-sensor is located on either the end plate or the re- turn bend of the condenser coil. A defrost cycle will initiate after the sensor closes (approx. 30° F) and remains closed for the length of time selected on the control board (either 30, 60 or 90 minutes)*.

At the start of the defrost cycle, the re- versing valve will change from heating to cooling mode. The condenser fan will also switch off there-by allowing pressure and temperature to rise within the condenser coil to melting off any ice build-up. At the same time the unit will switch on the in- door electric strip heater to temper the cold air being discharged from the evapo- rator unit. This will continue until either the defrost-sensor opens (approx. 60° F) or a 10-minute maximum cycle time has elapsed. Defrost times will vary depend- ing on outdoor temperature and moisture conditions. When the defrost cycle is com- plete the unit will return to normal heating operation.

*Factory settings 9-24k Btu = 90 minutesW

Side Discharge Condensers

20

www.enviromaster.com

Image 20
Contents Installation, operation and maintenance Manual Installation, operation and maintenance Manual S1C/S1H Single-Zone & S2C Dual-Zone Condensing UnitsControls and Components System OPTIOnsInstallation Instructions Items for ConsiderationS1C High Volt Connection Completed Electrical ConnectionsRefrigerant Piping Installation Instructions Trap Installation Clean the ends of tubing and insert into fittings Refrigerant Processing Installation Instructions Refrigerant Processing S2C Refrigerant Charge TableSingle Zone Operation Charts Single Zone Operation Charts Single Zone Operation Charts Single Zone Operation Charts Single Zone Heat Pump Operation Charts Single Zone Heat Pump Operation Charts Dual Zone Operation Charts Preperation for Start-Up Single-Zone and Dual-Zone Condenser Sequence of OperationFactory settings 9-24k Btu = 90 minutesW Single-Zone and Dual-Zone Sequence of OperationDefrost Control Board S1C/S1H Specifications and dimensions S2c specifications and dimensionsS1C Electrical Specifications S1H Electrical Specifications S2c Test Unit Performance Data sheet Test Unit Performance DataEMI’s Product Line Phone Success Drive Fax Rome, NY