ASSEMBLY |
-Introduce the bulb G of the limiter thermostat into the boiler
pocket.
- Connect the charging pump to the boiler control console, ensuring that the terminals live (L), neutral (N) and earth () are properly attached.
-Connect the probe bulb to the boiler control console.
- Introduce the probe bulb into the pocket of the sanitary hot |
|
|
|
|
|
|
|
| ||||
water tank. |
|
|
|
|
|
|
|
|
|
| ||
WARNING |
|
|
|
|
|
|
| |||||
If the tank is already fitted with a thermostat, it will not be used : |
|
|
|
|
|
|
|
|
|
| ||
accordingly replace the bulb of this thermostat with the tank probe. |
|
|
|
|
|
|
|
| ||||
IMPORTANT: Under no circumstances may the |
|
|
|
|
|
|
|
| ||||
wires of the probe (very low voltage) and wires |
|
|
|
|
|
|
| |||||
carrying 230 V supply feed be placed in the same |
|
|
|
|
|
|
|
|
| |||
conduit or cable duct. Make sure that a minimum |
|
|
|
|
|
|
|
|
| |||
interval of 10 cm is maintained between them. |
|
|
|
|
|
|
|
|
| |||
Failure to do so can cause interference and lead |
|
|
|
|
|
|
|
|
| |||
to malfunction of the control system and the |
|
|
|
|
|
|
|
|
| |||
deterioration of the electronic circuits. |
|
|
|
|
|
|
|
|
| |||
Securing the module |
|
|
|
|
|
|
|
|
|
| ||
Mount the module by the front so as to secure it with the help of the |
|
|
|
|
|
|
|
|
|
| ||
two screws located on the front section (use a cruciform (Phillips) |
|
|
|
|
|
|
|
|
|
| ||
screwdriver). |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
| ||||||
Connections (Installation with MB1 Module) |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| ||||||
|
|
|
|
|
| |||||||
|
|
|
| |||||||||
|
|
|
|
| ||||||||
| ||||||||||||
! |
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |||
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| ||
|
| "#$%% "#$%% | "#$%% |
|
|
|
|
|
-Move bridge TL from terminals
-Remove bridge LP from terminals
-Connect the power supply, the heating pump and the tank load pump as shown.
-Connect the tank sensor.
WARNING
If the installation includes an MB1 module and no room thermostat (TAM), set three position switch 5 (see page 14) to .
If the installation includes an MB1 module and a room thermostat (TAM), set three position switch 5 (see page 14) to AUTO.
18 | Buccaneer GT, Falcon GTE - Installation, Assembly & Servicing |