Multiquip MQP20P manual Outdoor Installation, Indoor Installation, Mounting, Generator Grounding

Page 15

installation

Outdoor Installation

Install the generator in a area that is free of debris, bystanders, and overhead obstructions. Make sure the generator is on secure level ground so that it cannot slide or shift around. Also install the generator in a manner so that the exhaust will not be discharged in the direction of nearby homes.

The installation site must be relatively free from moisture and dust. All electrical equipment should be protected from excessive moisture. Failure to do so will result in deterioration of the insulation and will result in short circuits and grounding.

Foreign materials such as dust, sand, lint and abrasive materials have a tendency to cause excessive wear to engine and alternator parts.

CAUTION

Pay close attention to ventilation when operating the generator inside tunnels and caves.The engine exhaust contains noxious elements. Engine exhaust must be routed to a ventilated area.

Indoor Installation

Exhaust gases from diesel engines are extremely poisonous. Whenever an engine is installed indoors the exhaust fumes must be vented to the outside. The engine should be installed at least two feet from any outside wall. Using an exhaust pipe which is too long or too small can cause excessive back pressure which will cause the engine to heat excessively and possibly burn the valves.

Mounting

The generator must be mounted on a solid foundation (such as concrete) and set firmly on the foundation to isolate vibration of the generator when it is running.The generator must sit at least 6 inches above the floor or grade level (in accordance to NFPA 110, Chapter 5-4.1).

Generator Grounding

To guard against electrical shock and possible damage to the equipment, it is important to provide a good EARTH ground.

Article 250 (Grounding) of the National Electrical Code (NEC) provides guidelines for proper grounding and specifies that the cable ground shall be connected to the grounding system of the building as close to the point of cable entry as practical.

NEC articles 250-64(b) and 250-66 set the following grounding requirements:

1.Use one of the following wire types to connect the generator to earth ground.

a.Copper — 8 AWG (5.3 mm2)

b.Aluminum — 6 AWG (8.4 mm2)

2.When grounding the generator (Figure 2) connect the ground cable between the lock washer and the nut on the generator and tighten the nut fully. Connect the other end of the ground cable to earth ground.

3.NEC article 250-52(c) specifies that the earth ground rod should be buried a minimum of 8 ft. into the ground.

NOTICE

When connecting the generator to any building electrical system, ALWAYS consult a licensed electrician.

MQP20P STANDBY GENERATOR • operation and parts manual — rev. #1 (11/28/11) — page 15

Image 15
Contents Model MQP20P Diesel engine exhaust and some Proposition 65 warningPage MQP20P Standby Generator Table of ContentsChoose from three easy options SaFeTY MeSSageS Safety InformationGeNeRaTOR SaFeTY GeNeRal SaFeTYRestricted. If the air fl ow is ENgiNe SaFeTYTOWiNg SaFeTY Fuel SaFeTYEleCTRiCal SaFeTY Grounding SafetyPower Cord/Cable Safety ENviRONMeNTal SaFeTY BaTTeRY SaFeTYSpecifications Dimensions Typical Generator Grounding Application InstallationGenerator Grounding Outdoor InstallationIndoor Installation MountingGeneral information GeneratorCamlok outlet box panel Principle of operation EngineElectrONIC Governor System Item no Description Major componentsBasic Engine Components Basic engine componentsMicroprocessor Engine Controller MEC Digital controller panelOutlet connectors Connector outlet box and main circuit breakerSingle Phase Load Load application/generator outputGenerator Amperage Fuel Check Inspection/setupRefueling Procedure Lubrication OilFuel Expands Coolant Antifreeze/summer coolant Cleaning the RadiatorAir Cleaner Fan Belt Tension BatteryPiping and Hose Connection Battery Cable InstallationWiring AlternatorStarting Manual Starting Auto ModeStartup Before StartingEmergency Shutdown Procedure Normal Shutdown ProcedureBattery Charger and Jacket Water Heater Power Connections JacketWater Heater and Internal Battery ChargerProtective devices Protective devicesTransporting TransportingMaintenance Air Filter Dust IndicatorGeneral Inspection Air Filter Fuel Tank Inspection Cleaning Inside the Fuel TankFuel Addition Removing Water from the Fuel TankPotentiometers Radiator CleaningVoltage regulator adjustments Flushing Out Radiator and Replacing CoolantGenerator Storage Adjustment ProcedureTroubleshooting Generator Troubleshooting GeneratorTroubleshooting Engine Troubleshooting engineTroubleshooting MEC20 Controller Troubleshooting controllerImproper calibration? Troubleshooting Voltage Regulator Troubleshooting Voltage RegulatorMaintenance Parts Locator Control BOX Generator Wiring Diagram single phaseCircuit Breaker BOX Generator Wiring Diagram three phase 505 K1 Explanation of Code in Remarks Column MQP20P with Perkins 404D-22 Diesel Engine 1 to 3 units Suggested Spare PartsHousing assy Part Name Engine and Generator Mounting assy GENERATOR, 30KW Fuel assy Part Name QTY Remarks Electrical assy BOLT, BATTERY, 10.38 Jacket Water HEater assy BRACKET, MOUNTING, Heater Solenoid assy BRACKET, Starter Solenoid Radiator assy Guard Air filter assy Cover Engine exhaust assy Exhaust Flex Engine Oil assy OIL Filler CAP Control panel assy PANEL, FRONT, Control Panel Controller assy MODULE, Output Expan MEC 2/20 W/CABLE Saddlebox assy Phase Units Circuit breaker assy Ground Camlok assy HousingCOVER, HINGED, Black FReigHT pOliCY Terms and Conditions of Sale PartsPage HERE’S HOW to GET Help