troubleshooting (controller)

CAUTION

Before opening the enclosure to perform troubleshooting or any service task, isolate the controller from any possible source of power. Failure to do so may result in serious personal injury or death due to electrical shock.

Troubleshooting (MEC20 Controller)

Symptom

Possible Problem

Solution

Does not power up even

 

Check wiring and repair. NOTE: The MEC 20 electronic

 

fuse triggers when there is an overload condition and does

with correct DC power

Wiring errors or short circuit?

not reset until the supply voltage is removed and overload

applied

 

 

condition is corrected.

 

 

 

 

 

 

 

Check that the "watchdog" LED on the rear of the PCB is

 

Microprocessor defective?

flashing red meaning that the microprocessor is working. If

 

 

not, repair or replace microprocessor.

LCD is not operational

Insufficient DC supply voltage?

Check voltage at input terminals B+ and B- (10-30 VDC).

 

 

Adjust LCD contrast potentiometer (R115) on the rear of

 

Bad LCD resolution?

PCB for good pixel resolution for the operating temperature

 

 

of the unit.

 

Controller not in OFF mode?

Check that the controller is set to the OFF mode before

Controller cannot be

resetting.

 

"reset"

Engine is running?

Check that the engine has come to a complete stop before

 

resetting.

 

 

 

Shutdown circuits reset?

Check that all shutdown circuits are reset (red shutdown

 

LED must be off).

 

 

 

 

Engine speed signal must be detected (speed signal green

No "RUN" output signal

No engine speed signal?

LED on) during cranking if the "run-output fail safe" feature

is enabled. Verify correct magnetic pick-up signal at cranking

 

 

 

(2.0 VAC min.)

 

 

Check that the RUN output LED (on the rear of the PCB) is

 

RUN output LED off?

on. If yes, verify relay contact operation on terminals #18 and

 

 

#19.

Overspeed shutdown occurs

 

Verify that the controller has been programmed with the correct

Controller not correctly programmed?

values for the number of flywheel teeth, nominal RPM, and

at normal speed

 

overspeed setpoint percentage.

 

 

 

 

Verify that the controller has been programmed with the correct

 

Controller not correctly programmed?

values for voltage sensing PT ratio and/or current sensing CT

 

 

ratio.

 

Battery not properly grounded?

Verify that the battery supply DC negative conductor is properly

 

grounded to the engine block (i.e. to a common ground point.)

Voltage or current metering

 

 

Verify that the controller's analog input has been properly

is reading incorrectly

Analog input not properly calibrated?

calibrated.

 

 

 

Verify that the voltage sensing wiring connection to the

 

Incorrect wiring?

controller matches power distribution type (Note: standard

 

direct voltage connection requires that the generator's neutral

 

 

 

 

is solidly grounded).

page 38 —MQP20P STANDBY GENERATOR • operation and parts manual — rev. #1 (11/28/11)

Image 38
Contents Model MQP20P Proposition 65 warning Diesel engine exhaust and somePage Table of Contents MQP20P Standby GeneratorChoose from three easy options Safety Information SaFeTY MeSSageSGeNeRal SaFeTY GeNeRaTOR SaFeTYENgiNe SaFeTY Restricted. If the air fl ow isFuel SaFeTY TOWiNg SaFeTYPower Cord/Cable Safety EleCTRiCal SaFeTYGrounding Safety BaTTeRY SaFeTY ENviRONMeNTal SaFeTYSpecifications Dimensions Installation Typical Generator Grounding ApplicationMounting Outdoor InstallationIndoor Installation Generator GroundingCamlok outlet box panel General informationGenerator ElectrONIC Governor System Principle of operationEngine Major components Item no DescriptionBasic engine components Basic Engine ComponentsDigital controller panel Microprocessor Engine Controller MECConnector outlet box and main circuit breaker Outlet connectorsGenerator Amperage Single Phase LoadLoad application/generator output Lubrication Oil Inspection/setupRefueling Procedure Fuel CheckFuel Expands Battery Cleaning the RadiatorAir Cleaner Fan Belt Tension Coolant Antifreeze/summer coolantAlternator Battery Cable InstallationWiring Piping and Hose ConnectionBefore Starting Starting Auto ModeStartup Starting ManualNormal Shutdown Procedure Emergency Shutdown ProcedureJacketWater Heater and Internal Battery Charger Battery Charger and Jacket Water Heater Power ConnectionsProtective devices Protective devicesTransporting TransportingGeneral Inspection Air Filter MaintenanceAir Filter Dust Indicator Removing Water from the Fuel Tank Cleaning Inside the Fuel TankFuel Addition Fuel Tank InspectionFlushing Out Radiator and Replacing Coolant Radiator CleaningVoltage regulator adjustments PotentiometersAdjustment Procedure Generator StorageTroubleshooting Generator Troubleshooting GeneratorTroubleshooting engine Troubleshooting EngineTroubleshooting controller Troubleshooting MEC20 ControllerImproper calibration? Troubleshooting Voltage Regulator Troubleshooting Voltage RegulatorMaintenance Parts Locator Generator Wiring Diagram single phase Control BOXCircuit Breaker BOX Generator Wiring Diagram three phase 505 K1 Explanation of Code in Remarks Column Suggested Spare Parts MQP20P with Perkins 404D-22 Diesel Engine 1 to 3 unitsHousing assy Part Name Engine and Generator Mounting assy GENERATOR, 30KW Fuel assy Part Name QTY Remarks Electrical assy BOLT, BATTERY, 10.38 Jacket Water HEater assy BRACKET, MOUNTING, Heater Solenoid assy BRACKET, Starter Solenoid Radiator assy Guard Air filter assy Cover Engine exhaust assy Exhaust Flex Engine Oil assy OIL Filler CAP Control panel assy PANEL, FRONT, Control Panel Controller assy MODULE, Output Expan MEC 2/20 W/CABLE Saddlebox assy Phase Units Circuit breaker assy Ground Housing Camlok assyCOVER, HINGED, Black Terms and Conditions of Sale Parts FReigHT pOliCYPage HERE’S HOW to GET Help