load application/generator output

Single Phase Load

Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage, frequency, and voltage requirements are satisfactorily supplied by the generator for operating the equipment.

Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130—150% more wattage than the rating on the nameplate, as the wattage is influenced by the efficiency, power factor and starting system of the equipment.

.NOTICE

If wattage is not given on the equipment’s name plate, approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 1.0. See Table 6 below when connecting loads.

Table 6. Power Factor By Load

 

Type of Load

 

 

Power Factor

Single-phase induction motors

 

 

0.4-0.75

 

 

 

 

Electric heaters, incandescent lamps

 

1.0

 

Fluorescent lamps, mercury lamps

 

0.4-0.9

Electronic devices, communication

 

1.0

 

equipment

 

 

 

 

 

 

 

 

 

 

 

 

Common power tools

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

Table 7. Cable Selection (60 Hz, Single Phase Operation)

 

 

 

 

 

 

 

 

Current

Load in Watts

Maximum Allowable Cable Length

 

 

 

 

 

 

 

 

in

At 100

At 200

#10 Wire

#12 Wire

#14 Wire

 

#16 Wire

Amperes

 

Volts

Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

300

600

1000 ft.

600 ft.

375 ft.

 

250 ft.

 

 

 

 

 

 

 

 

 

5

600

1200

500 ft.

300 ft.

200 ft.

 

125 ft.

 

 

 

 

 

 

 

 

 

7.5

900

1800

350 ft.

200 ft.

125 ft.

 

100 ft.

 

 

 

 

 

 

 

 

 

10

1200

2400

250 ft.

150 ft.

100 ft.

 

 

 

 

 

 

 

 

 

 

 

15

1800

3600

150 ft.

100 ft.

65 ft.

 

 

 

 

 

 

 

 

 

 

 

20

2400

4800

125 ft.

75 ft.

50 ft.

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage

 

 

 

 

 

 

 

 

 

 

NOTICE

Motors and motor-driven equipment draw much greater current for starting than during operation.

An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable. Refer to Table 7 to select the correct cable size.

„„When connecting a resistance load such as an incandescent lamp or electric heater, a capacity of up to the generator’s rated output (kW) can be used.

„„When connecting a fluorescent or mercury lamp, a capacity of up to the generator's rated output (kW) multiplied by 0.6 can be used.

„„When connecting an electric drill or other power tools, pay close attention to the required starting current capacity.

When connecting ordinary power tools, a capacity of up to the generator’s rated output (kW) multiplied by 0.8 can be used.

DANGER

Before connecting this generator to any building’s electrical system, a licensed electrician must install a transfer switch. Serious damage to the building’s electrical system may occur without this transfer switch.

Generator Amperage

Table 8 shows the maximum amps the generator can provide. DO NOT exceed the maximum amps as listed.

Table 8. Generator Maximum Amps

Rated Voltage

Maximum Amps

 

 

1Ø 120 Volt

83 X 2 amps (4 wire)

 

 

1Ø 240 Volt

83 amps (4 wire)

 

 

page 22 —MQP20P STANDBY GENERATOR • operation and parts manual — rev. #1 (11/28/11)

Image 22
Contents Model MQP20P Proposition 65 warning Diesel engine exhaust and somePage Table of Contents MQP20P Standby GeneratorChoose from three easy options Safety Information SaFeTY MeSSageSGeNeRal SaFeTY GeNeRaTOR SaFeTYENgiNe SaFeTY Restricted. If the air fl ow isFuel SaFeTY TOWiNg SaFeTYGrounding Safety EleCTRiCal SaFeTYPower Cord/Cable Safety BaTTeRY SaFeTY ENviRONMeNTal SaFeTYSpecifications Dimensions Installation Typical Generator Grounding ApplicationMounting Outdoor InstallationIndoor Installation Generator GroundingGenerator General informationCamlok outlet box panel Engine Principle of operationElectrONIC Governor System Major components Item no DescriptionBasic engine components Basic Engine ComponentsDigital controller panel Microprocessor Engine Controller MECConnector outlet box and main circuit breaker Outlet connectorsLoad application/generator output Single Phase LoadGenerator Amperage Lubrication Oil Inspection/setupRefueling Procedure Fuel CheckFuel Expands Battery Cleaning the RadiatorAir Cleaner Fan Belt Tension Coolant Antifreeze/summer coolantAlternator Battery Cable InstallationWiring Piping and Hose ConnectionBefore Starting Starting Auto ModeStartup Starting ManualNormal Shutdown Procedure Emergency Shutdown ProcedureJacketWater Heater and Internal Battery Charger Battery Charger and Jacket Water Heater Power ConnectionsProtective devices Protective devicesTransporting TransportingAir Filter Dust Indicator MaintenanceGeneral Inspection Air Filter Removing Water from the Fuel Tank Cleaning Inside the Fuel TankFuel Addition Fuel Tank InspectionFlushing Out Radiator and Replacing Coolant Radiator CleaningVoltage regulator adjustments PotentiometersAdjustment Procedure Generator StorageTroubleshooting Generator Troubleshooting GeneratorTroubleshooting engine Troubleshooting EngineTroubleshooting controller Troubleshooting MEC20 ControllerImproper calibration? Troubleshooting Voltage Regulator Troubleshooting Voltage RegulatorMaintenance Parts Locator Generator Wiring Diagram single phase Control BOXCircuit Breaker BOX Generator Wiring Diagram three phase 505 K1 Explanation of Code in Remarks Column Suggested Spare Parts MQP20P with Perkins 404D-22 Diesel Engine 1 to 3 unitsHousing assy Part Name Engine and Generator Mounting assy GENERATOR, 30KW Fuel assy Part Name QTY Remarks Electrical assy BOLT, BATTERY, 10.38 Jacket Water HEater assy BRACKET, MOUNTING, Heater Solenoid assy BRACKET, Starter Solenoid Radiator assy Guard Air filter assy Cover Engine exhaust assy Exhaust Flex Engine Oil assy OIL Filler CAP Control panel assy PANEL, FRONT, Control Panel Controller assy MODULE, Output Expan MEC 2/20 W/CABLE Saddlebox assy Phase Units Circuit breaker assy Ground Housing Camlok assyCOVER, HINGED, Black Terms and Conditions of Sale Parts FReigHT pOliCYPage HERE’S HOW to GET Help