startup
Before Starting
CAUTION
The engine’s exhaust contains harmful emissions.
ALWAYS have adequate ventilation when operating. Direct exhaust away from nearby personnel.
WARNING
NEVER manually start the engine with the main circuit breaker in the ON position.
1.Place the main circuit breaker (Figure 14) in the OFF position prior to starting the engine.
3.Listen for any abnormal noises. If any abnormalities exist, shut down the engine and correct the problem.
4.Using the controller display, verify that the
5.Place the main circuit breaker (Figure 16) to the ON position. Voltage is now available at the receptacles.
Figure 14. Main Circuit Breaker (OFF)
2.Connect the load to the receptacles on the Camlok outlet box. See Figure 6.
3.Tighten terminal nuts securely to prevent load wires from slipping out.
Starting (Manual)
1.Press the RUN button (Figure 15) on the controller to start the engine.
Figure 15. Run Button
Figure 16. Main Circuit Breaker (ON)
Starting (Auto Mode)
DANGER
Before connecting the generator to a building’s electrical system, a licensed electrician must install a transfer switch. Serious damage to the building’s electrical system may occur without a transfer switch.
CAUTION
When connecting the generator to an automatic transfer switch, ALWAYS have power applied to the generator’s internal battery charger.This will ensure that the engine will not fail due to a dead battery.
WARNING
When running the generator in the AUTO mode, the generator can start up at any time without warning. NEVER attempt to perform any maintenance when the generator is in the AUTO mode.
2.Once the engine starts, let the engine run for
NOTICE
When the generator is placed in the AUTO mode, the engine glow plugs will be warmed and the engine will start automatically.
MQP20P STANDBY GENERATOR • operation and parts manual — rev. #1 (11/28/11) — page 27