4Conversion to a different gas category
Caution
The conversion may only by carried out by an authorised installation
| engineer. | |
|
| |
| If the appliance must operate on a family of gases (LP gas or natural gas) or | |
| other gas category than that for which the appliance has been set at the | |
| factory, the appliance will have be adapted using a special conversion kit. | |
|
|
|
|
| Caution |
|
| You must check the supply pressure and burner pressure once the |
| conversion is complete. | |
4.1 Conversion |
|
|
1. | Isolate (10.3 "Isolating the appliance from the mains") the water heater from | |
|
| the power supply. |
| 2. | Shut off the gas supply. |
| 3. | Referring to the gas table (3.4.3 "Gas data"), determine whether the pilot |
|
| flame orifice for the intended gas category is different from the one that is |
|
| currently fitted. If so, replace (4.2 "Orifice replacement") it. |
|
|
|
|
| Note |
|
| The current gas category is stated on the type plate. |
|
|
|
| 4. | Referring to the gas table (3.4.3 "Gas data"), determine whether the main |
|
| orifice for the intended gas category is different from the one that is currently |
|
| fitted. If so, replace (4.2 "Orifice replacement") it. |
| 5. | Referring to the gas table (3.4.3 "Gas data"), determine whether the use of |
|
| a blank plate or burner pressure regulator is required for the intended gas |
|
| category. If this is different than for the current gas category, |
|
| exchange (4.3 "Replacement of burner pressure regulator or blank plate |
|
|
|
| 6. | Referring to the gas table (3.4.3 "Gas data"), determine whether the supply |
|
| pressure and burner pressure for the intended gas category correspond with |
|
| those for the current gas category, and adjust (3.11 "Checking the supply |
|
| pressure and burner pressure") these if necessary. |