A.O. Smith BFM - 100 Maximum floor load, Water composition, Working clearances, Installation

Models: BFM - 100 BFM - 120

1 74
Download 74 pages 2.7 Kb
Page 18
Image 18

3

3.3.2

3.3.3

Installation

is

 

Maximum floor load

Allow for the appliance's weight with respect to the maximum floor load; refer to the table.

Weight of the appliance filled with water

BFM 30

BFM 50

BFM 80

BFM 100

BFM 120

 

 

 

 

 

539 kg

543 kg

548 kg

573 kg

573 kg

 

 

 

 

 

Water composition

The appliance is intended for heating drinking water. The drinking water must comply with the regulations governing drinking water for human consumption. The table gives an overview of the specifications.

Water specifications

Water composition

Hardness

> 1.00 mmol/l:

(alkaline earth ions)

• German hardness> 5.6° dH

 

• French hardness > 10.0° fH

 

• English hardness > 7.0° eH

 

 

Conductivity

> 125 µS/cm

 

 

Acidity (pH value)

7.0 < pH value < 9.5

 

 

 

 

Note

If the water specifications deviate from those stated in the table, then the tank protection cannot be guaranteed (13 "Warranty (certificate)").

3.3.4Working clearances

For access to the appliance, it is recommended that the following clearances are observed (see figure):

AA: around the appliance's control column and cleaning openings: 100cm.

BB: all sides of the appliance: 50cm.

Above the appliance (room to replace the anodes):

-100cm if using fixed anodes, or

-50cm if using flexible anodes.

If the available clearance is less than 100cm, flexible magnesium anodes may be ordered.

Note

When installing the appliance, be aware that any leakage from the tank

and/or connections can cause damage to the immediate environment or floors below the level of the boiler room. If this is the case, the appliance should be installed above a wastewater drain or in a suitable metal leak tray.

The leak tray must have an appropriate wastewater drain and must be at least 5cm deep with a length and width at least 5cm greater than the diameter of the appliance.

18

Instruction manual BFM

Page 18
Image 18
A.O. Smith BFM - 100, BFM - 120 manual Maximum floor load, Water composition, Working clearances, Installation