3

3.4.3

Installation

Gas data

Gas data

is

Description

Unit

 

BFM

BFM

BFM

BFM

BFM

 

 

 

30

50

80

100

120

 

 

 

 

 

 

 

 

Gas category: 30 through 100 II2H3+, 120: II2H3P

 

 

 

 

 

Natural gas G20 - 20 mbar

 

 

 

 

 

 

 

Orifice diameter

mm

 

2.60

2.50

2.70

3.20

3.30

 

 

 

 

 

 

 

 

Diameter of pilot flame orifice

mm

 

0.56/0.41

0.56/0.41

0.56/0.41

0.56/0.41

0.56/0.41

 

 

 

 

 

 

 

 

(1) = Blank plate

1 or 2

 

2

2

2

2

2

(2) = Burner pressure regulator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal load (upper value)

kW

 

32.2

52.2

83.3

113.3

127.7

 

 

 

 

 

 

 

 

Nominal output

kW

 

26.4

42.3

67.5

90.8

102.4

 

 

 

 

 

 

 

 

Supply pressure

mbar

 

20

20

20

20

20

 

 

 

 

 

 

 

 

Burner pressure (†)

mbar

 

12.5

12.9

12.9

12.5

14.0

Gas consumption (*)

m3/h

 

3.1

5.0

7.9

10.8

12.2

LP gas data

 

 

 

 

 

 

 

G30 - 30 mbar (butane)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Orifice diameter

mm

 

1.45

1.40

1.50

1.95

n.a.

 

 

 

 

 

 

 

 

Diameter of pilot flame orifice

mm

 

0.25

0.25

0.25

0.25

 

 

 

 

 

 

 

 

 

(1) = Blank plate

1 or 2

 

1

1

1

1

 

(2) = Burner pressure regulator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal load (upper value)

kW

 

31.4

49.9

81.3

110.5

 

 

 

 

 

 

 

 

 

Nominal output

kW

 

26.4

41.4

67.5

90.8

 

 

 

 

 

 

 

 

 

Supply pressure

mbar

 

30

30

30

30

 

 

 

 

 

 

 

 

 

Burner pressure (†)

mbar

 

-

-

-

-

 

Gas consumption (*)

kg/h

 

2.3

3.6

5.9

8.0

 

G31 - 37mbar (propane)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Orifice diameter

mm

 

1.45

1.40

1.50

1.95

2.30

 

 

 

 

 

 

 

 

Diameter of pilot flame orifice

mm

 

0.25

0.25

0.25

0.25

0.25

 

 

 

 

 

 

 

 

(1) = Blank plate

1 or 2

 

1

1

1

1

2

(2) = Burner pressure regulator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal load (upper value)

kW

 

30.4

47.8

77.2

110.9

125.0

 

 

 

 

 

 

 

 

Nominal output

kW

 

25.5

39.6

63.9

90.8

102.4

 

 

 

 

 

 

 

 

Supply pressure

mbar

 

37

37

37

37

37

 

 

 

 

 

 

 

 

Burner pressure (†)

-

 

-

-

-

--

22.0

Gas consumption (*)

kg/h

 

2.2

3.4

5.5

7.9

8.9

(*) Based on 1013.25 mbar and 15 °C.

(†) If using a blank plate instead of a burner pressure regulator, it is assumed that the burner pressure is equal to the supply pressure. In practice, however, the burner pressure will be lower.

22

Instruction manual BFM

Page 22
Image 22
A.O. Smith BFM - 100, BFM - 120 manual Gas data, Description Unit, Natural gas G20 20 mbar, LP gas data G30 30 mbar butane