A.O. Smith BFM - 120, BFM - 100 manual Symptom Cause Solution Remark, Cycle

Models: BFM - 100 BFM - 120

1 74
Download 74 pages 2.7 Kb
Page 61
Image 61

 

 

 

 

 

is

 

 

 

 

 

Symptom

Cause

Solution

Remark

 

 

 

 

 

Burner control reset

There are three possible

causes for this error. In order to determine the cause, you must

see the appliance's heating cycle (9.3 "The appliance's heating

 

button (burner control

cause the error to appear again:

cycle")

lock out error)

1.

Reset the appliance by pressing the reset button 1x

 

 

 

 

 

 

2.

Cause (a) occurs between step 4 and step 5 of the heating cycle

 

 

 

3.

Cause (b) occurs in step 5 or 6

 

 

 

4.

Cause (c) occurs in step 7

 

 

 

 

 

 

 

 

 

(a) Continuous failure

1.

Check whether the thermostat is defective

If the error cannot be resolved or is persistent, contact your

 

in the safety circuit

2.

Check whether the sensor of the thermostat is defective

installation engineer

 

 

 

 

 

 

 

 

3.

Check the leads of the thermostat

 

 

 

 

 

 

 

 

(b) Failed start attempt

No gas:

If the error cannot be resolved or is persistent, contact your

 

 

 

1.

Check that the gas valve is open

installation engineer

 

 

 

 

 

 

 

 

2.

Check whether the gas control is opening (clicking of the gas

 

 

 

 

 

 

control)

 

 

 

 

 

3.

Check the leads of the gas control

 

 

No ignition:

1.Check whether the spark igniter is sparking in the pilot flame cap

2.Check the leads of the glow igniter

3.Check whether the spark igniter is correctly mounted in the bracket

No flame detection:

 

1.

Check whether the flame probe is defective

 

 

2.

Check that the flame probe leads are properly connected

 

 

 

 

 

(c) Failure in the safety

1.

Check whether the control thermostat is working

If the error cannot be resolved or is persistent, contact your

circuit during heating

2.

Check whether the high-limit thermostat is working

installation engineer

(the safety thermostat

 

 

 

 

has switched)

3.

Check that the circulation pump (if present) is working

 