An integrated, manually operated bypass unit ensures an uninterrupted supply to the connected loads in the case of maintenance and/or service work. The internal electronic part (with the exception of the
Number of | 1 | 2 | 3 | 4 | 5 | 6 | |
Load UPS modules | |||||||
module | modules | modules | modules | modules | modules | ||
4 kVA | no | n+1 | n+2 | n+3 | n+4 | n+5 | |
redundancy | (4 kVA) | (8 kVA) | (12 kVA) | (16 kVA) | (20 kVA) | ||
| |||||||
8 kVA |
| no | n+1 | n+2 | n+3 | n+4 | |
| redundancy | (4 kVA) | (8 kVA) | (12 kVA) | (16 kVA) | ||
|
| ||||||
12 kVA |
|
| no | n+1 | n+2 | n+3 | |
|
| redundancy | (4 kVA) | (8 kVA) | (12 kVA) | ||
|
|
| |||||
16 kVA | - - - |
|
| no | n+1 | n+2 | |
|
| redundancy | (4 kVA) | (8 kVA) | |||
|
| - - - |
| ||||
20 kVA |
| - - - |
| no | n+1 | ||
|
|
| |||||
|
|
| redundancy | (4 kVA) | |||
|
|
|
| - - - | |||
24 kVA |
|
|
| - - - | no | ||
|
|
|
| ||||
|
|
|
| redundancy | |||
|
|
|
|
|
| ||
|
|
|
|
|
|
|
Fig.: Table showing the level of redundancy depending on the installed modules and available output power
2.2 | Technical Data |
|
|
| Type rating |
|
|
| PROTECT 1.M (system) | max. 24 kVA (cos ϕ = 0.7 lag.) | |
|
| 16800 W | |
| PROTECT 1.040 (module) | 4000 VA (cos ϕ = 0.7 lag.) | |
|
| 2800 W | |
| UPS input | 3ph~ or 1ph~ / N / PE | |
| Rated connection voltage | 400 | V / 230 Vac (3ph~) or |
|
| 230 | V (1ph~) |
| Voltage range without | 277 | Vac – 520 Vac ±3% |
| battery operation | (Rectifier 3ph~) |
160 Vac – 300 Vac ±3% (Rectifier 1ph~)
10