| 176 VAC – 264 VAC ±3% | |
| (Bypass) | |
Frequency | 50 Hz / 60 Hz | |
| (Automatic detection) | |
Frequency tolerance range | ±4 Hz | |
Current consumption at full load (max.) | ||
PROTECT 1.M (system) | 44 A (3ph~) or 132 A (1ph~) / 155 | |
| A (Bypass) | |
PROTECT 1.040 (module) | 7.3 A (3ph~) or 22 A (1ph~) | |
System disturbance factor | λ ≥ 0.98 | |
UPS output |
|
|
Nominal voltage output | 220 / 230 / 240 Vac ±2% | |
| (configuration via "CompuWatch" | |
| software) | |
Nominal frequency | 50 Hz / 60 Hz ±0.2 Hz (dependent | |
| on mains frequency) | |
Type of voltage | Sine, distortion | |
| < 3% THD (linear load) | |
| < 6% THD | |
Crest factor | 3:1 |
|
Overload behaviour | Up to 105% continuous; | |
with mains supply | > 105% – < 130% for 30s | |
| 130% for 2s | |
| Following this, automatic, | |
| uninterrupted switchover to | |
| integrated bypass (SBS). | |
| ||
| continues to be present (switch | |
| back if overload decreases = load | |
| < 90%) |
|
Overload behaviour with | Up to 105% continuous; | |
battery operation | > 105% – < 130% for 30s | |
| 130% for 2s | |
3 x IN for 100 ms |