176 VAC – 264 VAC ±3%

 

(Bypass)

Frequency

50 Hz / 60 Hz

 

(Automatic detection)

Frequency tolerance range

±4 Hz

Current consumption at full load (max.)

PROTECT 1.M (system)

44 A (3ph~) or 132 A (1ph~) / 155

 

A (Bypass)

PROTECT 1.040 (module)

7.3 A (3ph~) or 22 A (1ph~)

System disturbance factor

λ ≥ 0.98

UPS output

 

 

Nominal voltage output

220 / 230 / 240 Vac ±2%

 

(configuration via "CompuWatch"

 

software)

Nominal frequency

50 Hz / 60 Hz ±0.2 Hz (dependent

 

on mains frequency)

Type of voltage

Sine, distortion

 

< 3% THD (linear load)

 

< 6% THD (non-linear load)

Crest factor

3:1

 

Overload behaviour

Up to 105% continuous;

with mains supply

> 105% – < 130% for 30s

 

130% for 2s

 

Following this, automatic,

 

uninterrupted switchover to

 

integrated bypass (SBS).

 

Switch-off after 1 min. if overload

 

continues to be present (switch

 

back if overload decreases = load

 

< 90%)

 

Overload behaviour with

Up to 105% continuous;

battery operation

> 105% – < 130% for 30s

 

130% for 2s

Short-circuit behaviour

3 x IN for 100 ms

11