Nominal DC voltage (intermediate circuit) 120 Vdc DC window 102 Vdc – 160 Vdc ±1%
Trickle charge voltage 137 Vdc ±1%
Battery charging current (max.) 3.5 Adc per UPS module
CommunicationInterfaces | RS232 | |
| RS485 | |
| Additionally: Communication slot | |
| for optional expansion cards (e.g. | |
| AS/400 / SNMP, etc.) | |
Shutdown software on CD | "CompuWatch" for all common | |
| operating systems, e.g. Windows, | |
| Linux, Mac, Unix, FreeBSD, | |
| Novell, Sun | |
General data |
|
|
Classification | VFI SS 111 acc. to IEC | |
| ||
Total efficiency |
|
|
PROTECT 1.M (system) | > 88% |
|
PROTECT 1.040 (module) | > 89% |
|
Inherent noise (1m distance) |
|
|
PROTECT 1.M (system) | < 62 dB(A) | |
PROTECT 1.040 (module) | < 55 dB(A) | |
Cooling type | Forced air cooling through | |
| ||
Operating temperature range | 0 °C to +40 °C | |
| Battery systems | |
| (recommended): | |
| +15°C to +25°C | |
Storage temperature range | 0°C to +40°C | |
Relative humidity | 20% – 90% | |
| 12 |
|