4.2Transport to Installation Site

The PROTECT 1.M is equipped with transport rolls for easy transport to the intended installation site. It is recommended to install the UPS where:

The connection work can be conveniently carried out;

There is enough space for proper operation and, if necessary, for periodic and extraordinary maintenance work; in this regard, the connection cables should be long enough to move the UPS (to open the UPS if necessary) without having to switch it off.

The UPS is protected against external atmospheric influences;

The humidity and the ambient temperature are within the limits;

The fire protection standards are observed.

The battery service life strongly depends on the ambient temperature. Ambient temperatures between +15 °C and +25 °C are optimum.

Attention!

Only transport the PROTECT 1.M in an upright position! Never tilt or cant it; avoid displacing the centre of gravity!

Make sure that no magnetic storage media are stored and/or operated close to PROTECT 1.M.

21