4.2Transport to Installation Site
The PROTECT 1.M is equipped with transport rolls for easy transport to the intended installation site. It is recommended to install the UPS where:
♦The connection work can be conveniently carried out;
♦There is enough space for proper operation and, if necessary, for periodic and extraordinary maintenance work; in this regard, the connection cables should be long enough to move the UPS (to open the UPS if necessary) without having to switch it off.
♦The UPS is protected against external atmospheric influences;
♦The humidity and the ambient temperature are within the limits;
♦The fire protection standards are observed.
The battery service life strongly depends on the ambient temperature. Ambient temperatures between +15 °C and +25 °C are optimum.
Attention!
Only transport the PROTECT 1.M in an upright position! Never tilt or cant it; avoid displacing the centre of gravity!
Make sure that no magnetic storage media are stored and/or operated close to PROTECT 1.M.