8 Operating and Maintenance
8.1Operation
1.Make sure that the phase sequence is correct if you are using a
2.Furthermore, make sure that the neutral conductor has been connected properly and that the system is adequately earthed.
3.Check the polarity of the battery system. Make sure that the (+) and
4.Switch the input protection switch on the rear of the UPS to "ON". The fans start operating immediately.
5.Now set the "system start switch" behind the slot cover cap of the LC display to "ON" and follow the instructions on the LC display.
Note: The diagrams below show examples for the displays with a
1) After step 4. |
| 2) Wait about 15 seconds | |
|
|
| IMPORTANT: Step 5 only now. |
|
|
|
|
LCD SELFTESTING … |
|
| Æ UPS ON |
|
|
| SETUP |
PT1.M UPS |
|
| INQUIRE |
UPS SELFTESTING |
|
|
|
PLEASE WAIT A MOMENT |
|
|
|
|
|
|
|
| 35 |
|