5) Select SETUP,

 

 

6) E.g. if the number of

e.g. REDUNDAN and

 

redundant modules is 0, …

press / Return

 

 

 

 

 

 

SETUP REDUNDANCE

 

WARNING:

TOTAL NUM:

3

 

CURRENT SETTING IS

ÆREDUN NUM:

1

 

NO REDUNDANCY, OK?

MAX POWER CURRENT

 

YES Æ NO

SETTING: 8kVA/5.6kW

 

 

 

 

 

The redundancy setup applies after the Setup menu is exited, i.e. the UPS displays "Overload" if the power is more than 8 kVA / 5.6 kW.

7)Switch on the PROTECT 1.M in battery mode:

Having ensured that the batteries are connected correctly, switch the battery fuse-switch disconnector to "ON". Then

press the system switch (located behind the LC display) from "OFF" to "ON". The displayed menu is similar to that of mains current mode. Now switch on the UPS. The UPS switches off if you do not start any action within 15 seconds; the LC display is switched off after about 10 minutes: "NO MODULE DETECTED"

Observe the safety precaution!

For personal safety reasons, do not switch on the

UPS when the mains is disconnected!

40