5) Select SETUP, |
|
| 6) E.g. if the number of |
e.g. REDUNDAN and |
| redundant modules is 0, … | |
press ↵ / Return |
|
|
|
|
|
| |
SETUP REDUNDANCE |
| WARNING: | |
TOTAL NUM: | 3 |
| CURRENT SETTING IS |
ÆREDUN NUM: | 1 |
| NO REDUNDANCY, OK? |
MAX POWER CURRENT |
| YES Æ NO | |
SETTING: 8kVA/5.6kW |
| ||
|
|
|
|
The redundancy setup applies after the Setup menu is exited, i.e. the UPS displays "Overload" if the power is more than 8 kVA / 5.6 kW.
7)Switch on the PROTECT 1.M in battery mode:
Having ensured that the batteries are connected correctly, switch the battery
press the system switch (located behind the LC display) from "OFF" to "ON". The displayed menu is similar to that of mains current mode. Now switch on the UPS. The UPS switches off if you do not start any action within 15 seconds; the LC display is switched off after about 10 minutes: "NO MODULE DETECTED"
Observe the safety precaution!
For personal safety reasons, do not switch on the
UPS when the mains is disconnected!
40