INSTALLATION AT DIFFERENT LEVELS

AP24BC250-3, AP24BCF300-3, AP40BC350-3, AP40BCF450-3 Manual

INSTALLATION AT DIFFERENT LEVELS

If the remote condensing unit is installed at a higher level than the cabinet (FIG. 6) insert a siphon in the return line at every 6 ft. of difference in height. If the remote condensing unit is installed at a lower level than the cabinet (FIG. 7) it is not necessary to insert any siphons.

FIG. 6

FIG. 7

Insert a siphon at the beginning (a) and at the end (b) of each riser

CONNECTION PIPING FOR REMOTE CONDENSING UNITS

MODEL

SUPPLY LINE DIA.

INTAKE LINE DIA.

AP24BC250-3

1/2"

1-1/8"

AP24BCF300-3

5/8"

1-3/8"

AP40BC350-3

5/8"

1-3/8"

AP40BCF450-3

7/8'

1-5/8"