External Connection
CAUTION!
At a switch mode load of 100% the neutral must be rated for 200% output phase current.
UPS | External | External | External PE | Maximum | External |
| Input | Input Cable | Cable | External | Output Cable |
| Fuses* FM | [mm2] | [mm2] | Output | [mm2] |
| [A] |
| Fuses* |
| |
|
|
| [A] |
| |
|
|
|
|
|
|
240kW | 500 | 2//120 | 95 | 400 | 2//95 |
|
|
|
|
|
|
320kW | 630 | 2//185 | 150 | 500 | 2//150 |
|
|
|
|
|
|
*DIN gL types
NOTICE!
All cable dimensions are recommended sizes only. Refer to local legal regulations.
UPS | External Alarm | External System | External Battery | External Battery |
| Cable max. | Earth Cable | Breaker | Cable [mm2] |
| [mm2] | [mm2]** | [A] |
|
|
|
|
|
|
240kW | 2 | 25 | 400 | 2//95 |
|
|
|
|
|
320kW | 2 | 25 | 500 | 2//150 |
|
|
|
|
|
PVC cables insulated to withstand ambient temperature of max. 30oC
** Must be rated as external PE cable if mains system is not supplying PE
NOTICE!
Install gland plate in bottom of unit.
10 | Installation Guide APC Silcon |