Programming Parameters
5.0 Programming Parameters
Below table shows operating parameters programmable from keyboard. Only qualified users should
5.1Parameters
Parameter | Setting* | Comments |
|
|
|
| ||
|
|
|
|
|
| |||
Bypass operation | YES, NO | YES will switch the system into bypass mode | ||||||
|
|
|
|
|
|
|
| |
| GB, D, F |
|
|
|
|
|
| |
Language | DK, S, SF | Language of text in display | ||||||
NL, PL, CZ | ||||||||
|
|
|
|
|
|
| ||
| E, P, SK, H |
|
|
|
|
|
| |
|
|
|
|
|
| |||
Autostart | YES, NO | Automatic restart by mains return | ||||||
(1 min.delay). Ensures quick battery recharge | ||||||||
|
| |||||||
|
|
|
|
|
| |||
Remote shutdown active | YES, NO | Shutdown of UPS by remote signal when in | ||||||
battery operation. Saves battery energy | ||||||||
|
| |||||||
|
|
|
|
|
| |||
Remote shutdown | HIGH, LOW | Nature of remote shutdown signal level | ||||||
|
|
|
|
|
|
|
| |
| 0, 1, 2, 3, 4 |
|
|
|
|
|
| |
Remote shutdown time | 5, 6, 7, 8, 9 | Time delay on remote shutdown of UPS | ||||||
| 10 min. |
|
|
|
|
|
| |
|
|
|
|
|
| |||
|
| Initiates | ||||||
Battery capacity test | Time measured from start until it reaches low | |||||||
DC warning level. |
| |||||||
|
|
| ||||||
|
| (See User Guide section 6 ) | ||||||
|
|
|
|
|
| |||
Battery monitor test** | Initiates checks of battery condition by 25% | |||||||
discharging |
|
|
|
| ||||
|
|
|
|
|
| |||
|
|
|
|
|
| |||
Automatic battery test** | OFF, 3, 6 months | Activates the battery monitor test in cyclic | ||||||
intervals |
|
|
|
| ||||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
| ||
Battery monitor reset** | Press the |
| and |
|
| key | ||
|
| |||||||
|
|
|
|
|
| |||
to resets alarm (flashing light)! | ||||||||
|
| |||||||
|
|
|
|
|
| |||
Boost charge | YES, NO | YES results in boost charge (10 hours) | ||||||
|
|
|
|
|
| |||
Autoboost charge | YES, NO | YES results in boost charge after battery | ||||||
operation. (10 hours) |
| |||||||
|
|
| ||||||
|
|
|
|
|
|
| ||
Enter new date | YYMMDD | Set tolocal date |
| |||||
|
|
|
|
|
| |||
Enter new time | HHMMSS | Set to local time (24 hour clock) | ||||||
|
|
|
|
|
|
|
|
*Factory settings in bold
**Only for systems with Battery Monitor active
***Do not leave system running in bypass mode (Static bypass) for extended periodes of time, as batteries are not recharged in bypass mode.
Installation Guide APC Silcon | 35 |