Options/Accessories

6.0 Options/Accessories

Please contact your local APC representative for information on options/accessories available in your region. See “How to Contact APC” in this guide.

6.1Service Bypass Panel for Single Operation

UPS

External

Max.

System

System

Max.

Dimensions

Weight

Fixing

 

System

Prospec-

Input/

Output/

External

HxWxD [mm]

[kg]

Centres

 

Input

tive

UPS

UPS

System

 

 

AxB

 

Fuse

Short-

Input

Output

Output

 

 

[mm]

 

[A]

Circuit

Cable

Cable

Fuse

 

 

 

 

 

Current

[mm2]

[mm2]

[A]***

 

 

 

 

 

[kA]

**

**

 

 

 

 

 

 

 

 

 

 

 

 

 

240kW

500

45

2x120

2x95

400

1272x775

175

-

 

 

 

 

 

 

x350(410*)

 

 

320

 

 

 

 

 

 

 

 

kW

630

45

2x185

2x150

500

1825x

230

-

 

 

 

 

 

 

1160x620

 

 

 

 

 

 

 

 

(680*)

 

 

 

 

 

 

 

 

 

 

 

***If no external System Output fuses are available or if it has a higher value than indicated above, System Output and UPS Output cables should be dimensioned as System Input and UPS Input cables.

**Sizes according to IEC 364-5-532 for PVC insulated copper cables (max. ambient temperature: 30oC). Installation method B: Insulated conductors in wall conduit.

Also refer to local legal regulations.

Beware that single-phase Switch Mode Power supply loads will increase neutral current! At a 100% SMPS load, neutral cable should be dimensioned for 200% of phase current.

*Depth of enclosure includes switch handles

990-4045a

Installation Guide APC Silcon 240-320kW 400V UPS

43

Page 43
Image 43
American Power Conversion 240-320kW 400V manual Options/Accessories, Service Bypass Panel for Single Operation