External Connection
4.4.1 Relay Board/Relay Functions
NOTICE
If alarm mode “Communication to controller lost” is active, ALL relays will indicate failure
| Relay | Message |
|
|
| |
| Number |
|
|
|
| |
|
|
|
|
|
| |
| 1 ## (X002) | Mains outside limits | Mains voltage RMS outside limits |
|
| |
|
|
|
| Mains wave form (fast detector) outside limits |
|
|
|
|
|
| Mains frequency outside limits |
|
|
|
|
|
|
|
| |
| 2 ## (X003) | Bypass outside limits | Bypass voltage RMS outside limits |
|
| |
|
|
|
| Bypass wave form (fast detector) outside limits |
|
|
|
|
|
| Bypass frequency outside limits |
|
|
|
|
|
|
|
|
|
| 3 ## | (X004) | Output outside limits | Output voltage RMS value outside limits |
|
|
|
|
|
| Output wave form (fast detector) outside limits |
|
|
|
|
|
| Output frequency outside limits |
|
|
|
|
|
|
|
|
|
| 4 | (X005) | System overload | Output load exceeding 100% |
|
|
|
|
|
| Delta inverter current limiter active |
|
|
|
|
|
| Main inverter current limiter active |
|
|
|
|
|
|
|
|
|
| 5 | (X006) | Fan fault | Blocked or faulty fan |
|
|
|
|
|
|
|
|
|
| 6 | (X007) | High Equipment | Static switch temperature too high |
|
|
|
|
| Temperature or | Main inverter failure (temperature too high or fuse blown) |
| |
|
|
| Inverter Fuse Blown | Delta inverter temperature too high |
|
|
|
|
|
| Magnetic temperature too high |
|
|
|
|
|
| Isolation transformer (option) temperature too high |
|
|
|
|
|
| Battery temperature too high |
|
|
|
|
|
|
|
|
|
| 7 | (X008) | MCCB battery off | Battery MCCB/Fuse not closed or released |
|
|
|
|
|
|
|
|
|
| 8 | (X009) | Normal operation | UPS running in normal operation mode(status) |
|
|
|
|
|
|
|
| |
| 9 ## (X010) | Battery operation | UPS running in battery operation mode(status) |
|
| |
|
|
|
|
|
| |
| 10 ## (X011) | Bypass operation | UPS running in bypass operation mode(status) |
|
| |
|
|
|
|
|
| |
| 11 ## (X012) | UPS in |
|
| ||
|
|
|
| (Hot |
|
|
|
|
|
|
|
|
|
| 12 | (X013) | Service bypass | Service bypass switch active |
|
|
|
|
| operation |
|
|
|
|
|
|
|
|
| |
| 13 ## (X014) | Boost charge | UPS |
|
| |
|
|
| operation |
|
|
|
|
|
|
|
|
|
|
| 14 | (X015) | Battery voltage | DC voltage too high (shut down) |
|
|
|
|
| outside limits | DC voltage below warning level |
|
|
|
|
|
| DC voltage too low (shut down) |
|
|
|
|
|
|
|
|
|
| 15 | (X016) | Battery condition | ABM has detected weak battery condition |
|
|
|
|
| fault | ABM has detected defect battery |
|
|
|
|
|
| (ABM = Advanced Battery Monitor) |
|
|
|
|
|
|
|
| |
| 16 ## (X017) | Common fault | All alarms as mentioned above |
|
| |
|
|
|
| (except relays 8+9+10+11) |
|
|
|
|
|
| Internal power supply fault |
|
|
|
|
|
| System locked in operation mode |
|
|
|
|
|
| Internal memory fault |
|
|
|
|
|
| Internal communication fault |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
| |
Installation Guide APC Silcon | 17 |