MasterSwitch 100V – User Guide

 

 

 

 

 

 

 

 

 

 

 

Auto Power On

The Auto Power On selection allows the user to configure the receptacle to power-up and reboot independently or with the master:

--- Auto Power On -----------------------------

1- With Master

2- 15 Sec After Master

3- 30 Sec After Master

4- 45 Sec After Master

5- 1 Min After Master

6- 2 Min After Master

7- 5 Min After Master

8- Never

<ENTER> Redisplay Menu

<ESC> Return To Previous Menu

Figure 7: Auto Power On Submenu

Select one of the settings. Selecting “With Master” indicates that user-selected settings for the master outlet will also apply to this outlet. For more discussion of the master outlet, see below.

Master Outlet Configuration and Control

From the Outlets Manager submenu (see Figure 3), Option 9 allows the user to configure/control master settings to apply to all outlets whose Auto Power On settings are set to “With Master.” To perform an action on all outlets assigned to the master outlet, select Option 1 from the Outlets Manager submenu shown in Figure 3. The following submenu appears:

---- Control of

Master Outlet

-----------------------------------------------

Outlet

Device Name

Auto Power On

Reboot Duration

---------------------------------------------------------------------

1:ON

Device 1

With Master

Same as Master

2:ON

Device 2

With Master

Same as Master

3:ON

Device 3

With Master

Same as Master

4:ON

Device 4

With Master

Same as Master

5:ON

Device 5

With Master

Same as Master

6:ON

Device 6

With Master

Same as Master

7:ON

Device 7

With Master

Same as Master

8:ON

Device 8

With Master

Same as Master

Master

PDU

Immediate

5 Seconds

1- Immediate All On

2- Immediate All Off

3- Sequence All On

4- Immediate Reboot

5- Sequenced Reboot

?- Help

<ENTER> Redisplay Menu

<ESC> Return To Previous Menu

Figure 8: Master Control Menu

Page 20