31

 

 

 

31

 

MasterSwitch 100V – User Guide

 

 

 

 

 

 

 

 

 

 

Outlet Configuration (sPDUOutletConfig) OIDs

The sPDUOutletConfig OIDs consist of an sPDUOutletConfigTableSize read-only OID that defines the number of outlets (always 8), as well as one set of identical OIDs for each outlet, each set consisting of:

qAn sPDUOutletConfigIndex read-only OID that identifies the outlet.

qAn sPDUOutletPowerOnTime OID that allows you to define how much time, if any, in seconds, the outlet will delay providing output power when master power is newly applied:

-1(for never power on automatically)

0 (no delay: power on with master)

15 (for 15-second delay)

30 (for 30-second delay)

45 (for 45-second delay)

60 (for 1-minute delay)

120 (for 2-minute delay)

300 (for 5-minute delay)

qAn sPDUOutletName OID that allows you to define an up to 20-character long device name for the outlet.

Traps

The MasterSwitch can send eight different MasterSwitch-MIBtraps and three MIB-II traps.

MasterSwitch-MIB Traps

The following table briefly identifies and describes the eight MasterSwitch-MIBtraps.

MasterSwitch-MIBTrap

Index Number - Description

outletOn

41

- The specified outlet has been turned on (if 0, all outlets have been turned on).

outletOff

42

- The specified outlet has been turned off (if 0, all outlets have been turned off).

outletReboot

43

- The specified outlet has been rebooted (if 0, all outlets have been rebooted).

configChangeSNMP

44

- The SNMP configuration has been changed.

configChangeOutlet

45

- The specified outlet has changed configuration (if 0, the master outlet has changed

 

 

configuration.

accessViolationConsole

46

- Three unsuccessful terminal console logins have occurred.

configViolationHTTP

47

- An unsuccessful HTTP login has occurred.

passwordChange

48 - The password for the MasterSwitch has changed.

MIB-II Traps

The following table briefly identifies and describes the three MIB-II traps.

MIB-II Traps

Index Number - Description

coldStart

0

-

The MasterSwitch has been turned on.

warmStart

1

-

A MasterSwitch reinitialization has occurred.

snmpAuthenticationFailure 4

-

An attempt to use SNMP to access the MasterSwitch, while using an incorrect

 

 

 

community name, has occurred.

Page 31
Image 31
American Power Conversion AP9210 Outlet Configuration sPDUOutletConfig OIDs, MasterSwitch-MIB Traps, MIB-II Traps