Managing MasterSwitch VM

Management Interfaces continued

Control Console

In addition to using the Web, you can also manage MasterSwitch VM

interface

through the Control Console by one of the following modes of access:

 

Telnet, for remote management

 

A serial connection, for local management.

 

Telnet. To access the MasterSwitch VM unit’s Control Console using

 

Telnet:

 

 

 

 

 

1.

Start a Telnet session and choose Remote System from the

 

 

Connect pull-down menu.

 

 

 

2.

Type in the IP address of the MasterSwitch VM unit.

 

3.

Click on the Connect button.

 

 

 

Serial connection. To access the Control Console using a serial

 

connection:

 

 

 

1.

Use the supplied configuration cable (APC part number 940-

 

 

0024C) to connect your serial port to the configuration port on

 

 

the MasterSwitch VM Controller.

 

2.

Set the terminal port for the following communication settings:

 

 

 

 

 

 

 

 

 

Item

Setting

 

 

 

 

 

 

 

 

 

 

Baud Rate

2400

 

 

 

 

 

 

 

 

 

 

Data Bits

8

 

 

 

 

 

 

 

 

 

 

Stop Bits

1

 

 

 

 

 

 

 

 

 

 

Parity

None

 

 

 

 

 

 

 

 

 

 

Handshaking

None

 

 

 

 

 

 

 

 

 

 

Local Echo

Off

 

 

 

 

 

 

 

 

 

 

Terminal Type

ANSI (VT100)

 

 

 

 

 

 

 

Logging on. The procedure for logging on to the Control Console is the same for both Telnet and a serial connection; respond to the user name and password prompts.The default values of Administrator name and password are both apc, all lowercase. You can change the username, password and time-out values through the System menu. See User Manager on page 23.

Structure. All menus in the Control Console list items by number and name. To select an item, type in the number and press ENTER. For menus that configure values, always use the Accept Changes option to save any changes you have made.