Menu Items

MasterSwitch VM

Unit Configuration

Item

Definition

 

 

 

 

Name

Name of the MasterSwitch VM unit (23 characters

 

maximum).

 

 

 

 

 

 

 

The time that MasterSwitch VM will delay in applying power

 

Cold Start Delay

to outlets, once the AC power is applied to the MasterSwitch

 

 

VM unit.

 

 

 

 

 

The percentage of a full load that will trigger an overload

 

Overload Warning

warning. An overload warning will cause the overcurrent

 

Threshold

alarm LED to flash green and sound the audible alarm (if the

 

 

overload audible alarm property is configured to do so).

 

 

 

 

 

The overload conditions, if any, that will prevent outlets from

 

 

turning on. The following actions are available under this

 

 

item:

 

Overload Outlet

None—Always allow outlets to be turned on.

 

Restrictions

On Warning—Do not allow outlets to be turned on when the

 

 

Overload Warning Threshold has been exceeded.

 

 

On Overload—Do not allow outlets to be turned on when

 

 

the load exceeds 100%.

 

 

 

 

 

The overload conditions, if any, that will cause the audible

 

 

alarm to sound. Once the alarm starts sounding, you can

 

 

use the mute button to turn off the alarm or you can clear the

 

 

alarm; selecting Disabled will not clear the alarm. The

 

 

following actions are available under this item:

 

 

Disabled—Disables the audible alarm.

 

 

On Overload—Sounds the audible alarm when the load

 

Overload Audible

exceeds 100%.

 

Alarm

On Overload Warning—Sounds the audible alarm when the

 

 

load exceeds the Overload Warning Threshold.

 

 

Note: When you change settings, the new setting is not

 

 

used until the next time the event occurs. For

 

 

example, if the overload warning Threshold has

 

 

been exceeded and the setting is then changed from

 

 

On Overload to On Warning, the audible alarm will

 

 

not be activated.

 

 

 

 

Low Current

The threshold for load current below which an SNMP trap is

 

Threshold

generated..

 

 

 

 

 

Longest reboot duration in the set of accessible outlets. You

 

Reboot Duration

can change this value only by modifying the reboot duration

 

of accessible outlets. Used by Sequenced Reboot and

 

 

 

 

Delayed Sequenced Reboot.

 

 

 

 

 

Continued on next page

MasterSwitch VM User’s Guide

16

Page 21
Image 21
American Power Conversion AP9222EXP manual MasterSwitch VM, Unit Configuration