Introduction

Product Description continued

LEDs

LED

Status

Description

 

 

 

MasterSwitch VM

On

The Outlet is on.

Outlets

 

 

Off

The Outlet is off.

page 1, Item 2

 

 

 

 

 

 

Off

The unit has no power.

 

 

 

MasterSwitch VM

Green

The unit is operating under normal load

conditions.

 

Overcurrent Alarm

 

 

Flashing

The unit is approaching its maximum load.

 

page 1, Item 5

green

(Warning threshold exceeded)

 

 

 

 

Solid red

The unit has exceeded its maximum load.

 

(>100%)

 

 

 

 

 

MasterSwitch VM

On

The Controller has power.

Controller

 

 

 

 

Front Status

Off

The Controller has no power.

 

page 2, Item 1

 

 

 

 

 

 

Off

The unit has no power.

 

 

 

 

Solid green

The unit has valid network settings.

MasterSwitch VM

 

 

Flashing

The unit does not have valid network

Controller

green

settings.

Rear Status

 

 

page 2, Item 6

Solid red

A hardware failure has been detected in the

unit.

 

 

 

 

 

Blinking

The unit is making BOOTP requests.

 

Red (Slow)

 

 

 

 

 

MasterSwitch VM

 

The device which connects the unit to the

Off

network (whether a router, hub, or

Controller Rear

concentrator) is off or not operating

 

Link-RX/TX

 

correctly.

 

 

 

page 2, Item 7

Flashing

The unit is receiving data packets from the

 

Green

network.

 

 

 