4.7.6.2 Power, Physical, and Environmental Specifications.

 

 

 

 

 

Item

Specification

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

Turn on voltage:

> 22 VDC

 

 

 

 

 

 

Turn off voltage:

< 16 VDC

 

 

 

 

 

 

Current draw (normal operation):

90 mADC

 

 

 

 

 

 

Current draw

 

 

 

(voltage < 16 VDC):

< 1 mADC

 

 

 

 

 

 

Physical

 

 

 

 

 

 

 

Size (H xW x D):

44 x 432 x 127 mm

 

 

 

 

 

 

Weight:

1.81 kg

 

 

 

 

 

 

Shipping weight:

3.65 kg

 

 

 

 

 

 

Environmental

 

 

 

 

 

 

 

Elevation (above MSL):

 

 

 

Operating

0 to 3000 m

 

 

Storage

0 to 15 000 m

 

 

 

 

 

 

Temperature:

 

 

 

Operating

0 to 45˚C

 

 

Storage

-20 to 70˚C

 

 

 

 

 

 

Relative humidity:

 

 

 

Operating

0 to 95%, non-condensing

 

 

Storage

0 to 95%, non-condensing

 

 

 

 

 

 

Electromagnetic immunity:

FCC Class A

 

 

EN50082-1 verified

 

 

 

 

 

 

 

 