External Connection

UPS

External

External

External PE

Maximum

External

 

Input

Input Cable

Cable

External

Output Cable

 

Fuses* FM

[mm2]

[mm2]

Output

[mm2]

 

[A]

380-415V

 

Fuses*

 

 

380-415V

 

 

[A]

 

 

 

 

 

 

 

240kW

500

2//125

100

400

2//100

 

 

 

 

 

 

320kW

630

2//200

150

500

2//150

 

 

 

 

 

 

* DIN gL types

NOTICE!

All cable dimensions are recommended sizes only.

Refer to local legal regulations.

UPS

External Alarm

External System

External Battery

External Battery

 

Cable max.

Earth Cable

Breaker

Cable [mm2]

 

[mm2]

[mm2]**

[A]

 

 

 

 

 

 

240kW

2

30

400

2//100

 

 

 

 

 

320kW

2

30

500

2//150

 

 

 

 

 

PVC cables insulated to withstand ambient temperature of max. 30°C

** Must be rated as external PE cable if mains system is not supplying PE

NOTICE!

Install gland plate in bottom of unit.

 

990-4056

 

 

Installation Guide APC Silcon 240-320kW 400V UPS