External Connection
| UPS | External | External | External PE | Maximum | External | 
| 
 | Input | Input Cable | Cable | External | Output Cable | 
| 
 | Fuses* FM | [mm2] | [mm2] | Output | [mm2] | 
| 
 | [A] | 
 | 
 | Fuses* | 
 | 
| 
 | 
 | 
 | 
 | [A] | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
| 240kW | 500 | 2//125 | 100 | 400 | 2//100 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
| 320kW | 630 | 2//200 | 150 | 500 | 2//150 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
* DIN gL types
NOTICE!
All cable dimensions are recommended sizes only.
Refer to local legal regulations.
| UPS | External Alarm | External System | External Battery | External Battery | 
| 
 | Cable max. | Earth Cable | Breaker | Cable [mm2] | 
| 
 | [mm2] | [mm2]** | [A] | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
| 240kW | 2 | 30 | 400 | 2//100 | 
| 
 | 
 | 
 | 
 | 
 | 
| 320kW | 2 | 30 | 500 | 2//150 | 
| 
 | 
 | 
 | 
 | 
 | 
PVC cables insulated to withstand ambient temperature of max. 30°C
** Must be rated as external PE cable if mains system is not supplying PE
NOTICE!
Install gland plate in bottom of unit.
| 
 | |
| 
 | 
 | 
| Installation Guide APC Silcon  | 9 | 