External Connection
UPS | External | External | External PE | Maximum | External |
| Input | Input Cable | Cable | External | Output Cable |
| Fuses* FM | [mm2] | [mm2] | Output | [mm2] |
| [A] |
|
| Fuses* |
|
|
|
|
| [A] |
|
|
|
|
|
|
|
240kW | 500 | 2//125 | 100 | 400 | 2//100 |
|
|
|
|
|
|
320kW | 630 | 2//200 | 150 | 500 | 2//150 |
|
|
|
|
|
|
* DIN gL types
NOTICE!
All cable dimensions are recommended sizes only.
Refer to local legal regulations.
UPS | External Alarm | External System | External Battery | External Battery |
| Cable max. | Earth Cable | Breaker | Cable [mm2] |
| [mm2] | [mm2]** | [A] |
|
|
|
|
|
|
240kW | 2 | 30 | 400 | 2//100 |
|
|
|
|
|
320kW | 2 | 30 | 500 | 2//150 |
|
|
|
|
|
PVC cables insulated to withstand ambient temperature of max. 30°C
** Must be rated as external PE cable if mains system is not supplying PE
NOTICE!
Install gland plate in bottom of unit.
| |
|
|
Installation Guide APC Silcon | 9 |