American Power Conversion AP9604S Ampere Connection Max Dimensions Weight Rating Cable, HxWxD mm

Models: AP9604S

1 73
Download 73 pages 10.24 Kb
Page 31
Image 31

External Connection

UPS

Ampere

Connection

Max.

Dimensions

Weight

 

Rating

Cable

short-

HxWxD [mm]

[kg]

 

[A]

[mm2]

circuit

 

 

 

 

 

current [kA]

 

 

 

 

 

 

 

 

240 kW

400

2//100

40

1035x835x300

100

320 kW

500

2//150

40

1035x835x300

100

 

 

 

 

 

 

4.9.2 APC Battery Breaker Box Connection Diagram (120-480kW)

Battery 1

Battery 2

UPS Battery 1

UPS Battery 2

Main cables are connected directly

to component terminals

X009 LED signal from UPS “OK to operate corresponding MCCB”

X010 MCCB position signals for UPS

X011 Trip for emergency stop (220-240V AC)

990-4056

Installation Guide APC Silcon 240-320kW 400V UPS

31

Page 31
Image 31
American Power Conversion AP9604S manual Ampere Connection Max Dimensions Weight Rating Cable, HxWxD mm, Circuit