American Power Conversion AP9604S manual Order of Management Peripheral Cards

Models: AP9604S

1 73
Download 73 pages 10.24 Kb
Page 22
Image 22

External Connection

4.7.3.1 Order of Management Peripheral Cards

Because UPS signals are passed between management peripherals, you must install management peripheral cards in the correct order for them to work together properly. The card slots are numbered 1 to 3, from left to right, as viewed from the rear of the chassis. The following table lists the management peripheral cards, their priority, and proper position.

Management Peripheral

P/N

Priority

Position

Card

 

 

 

 

 

 

 

 

 

Web/SNMP Management

AP9606

Highest

High-numbered slot

Card

 

 

 

 

 

 

 

 

 

 

 

Out-of-Band Management

 

 

 

 

 

 

 

 

Card

AP9608

Second-highest

 

 

(Call-UPS®II)

 

 

 

 

Interface Expander

AP9607

Second lowest

 

 

 

 

 

 

 

Environmental Monitoring

AP9612T

Lowest

 

 

Card (Measure-UPS®II)

AP9612TH

Low-numbered slot

 

 

 

 

 

 

 

 

 

4.7.3.2 Installing Management Peripheral Cards

To install management peripherals, perform the following steps.

1)Make sure that the chassis is powered off.

2)Install management peripheral cards into the housings on the rear of the chassis. See the instructions supplied with the cards and the table above.

3)If you are daisy-chaining other APC external management peripherals to the APC Silcon Triple Chassis: Connect the UPS cable (supplied with the management peripheral) to the Monitoring port of the chassis and to the “To UPS” port of the other management peripheral (Share-UPS, MasterSwitch, etc.). See “Daisy-chaining the APC Silcon Triple Chassis”.

4)Power the APC Silcon Triple Chassis and all external management peripherals.

NOTICE!

If your configuration requires additional power, connect a 24V AC/DC power adapter available from APC (part number AP9505 or AP9505i) for all models of Triple Chassis.

4.7.3.3 Daisy-chaining the APC Silcon Triple Chassis

If you need more than the three card slots available with the APC Silcon Triple Chassis, or if you want to use other external management peripherals, you can daisy-chain external management peripherals together, provided that the total amperage of all installed management peripherals — cards and external — does not exceed the supplied amperage. (See “Determining Power Requirements:”).

NOTICE!

When daisy-chaining Triple Chassis units, you may need to use a power adapter.

990-4056