American Power Conversion AP9604S manual Relay Board/Relay Functions

Models: AP9604S

1 73
Download 73 pages 10.24 Kb
Page 16
Image 16

External Connection

4.4.1 Relay Board/Relay Functions

NOTICE

If alarm mode “Communication to controller lost” is active, ALL relays will indicate failure

Relay Number

Message

Alarm-trigging Events

 

 

 

1 ## (X002)

Mains outside limits

Mains voltage RMS outside limits

 

 

 

Mains wave form (fast detector) outside limits

 

 

 

Mains frequency outside limits

 

 

 

2 ## (X003)

Bypass outside limits

Bypass voltage RMS outside limits

 

 

 

Bypass wave form (fast detector) outside limits

 

 

 

Bypass frequency outside limits

 

 

 

 

3 ##

(X004)

Output outside limits

Output voltage RMS value outside limits

 

 

 

Output wave form (fast detector) outside limits

 

 

 

Output frequency outside limits

 

 

 

 

4

(X005)

System overload

Output load exceeding 100%

 

 

 

Delta inverter current limiter active

 

 

 

Main inverter current limiter active

 

 

 

 

5

(X006)

Fan fault

Blocked or faulty fan

 

 

 

 

6

(X007)

High Equipment

Static switch temperature too high

 

 

Temperature or

Main inverter failure (temperature too high or fuse blown)

 

 

Inverter Fuse Blown

Delta inverter temperature too high

 

 

 

Magnetic temperature too high

 

 

 

Isolation transformer (option) temperature too high

 

 

 

Battery temperature too high

 

 

 

 

7

(X008)

MCCB battery off

Battery MCCB/Fuse not closed or released

 

 

 

 

8

(X009)

Normal operation

UPS running in normal operation mode

 

 

 

(status)

 

 

 

9 ## (X010)

Battery operation

UPS running in battery operation mode

 

 

 

(status)

 

 

 

10 ## (X011)

Bypass operation

UPS running in bypass operation mode

 

 

 

(status)

 

 

 

11 ## (X012)

Stand-by operation

UPS in stand-by mode

 

 

 

(Hot stand-by - parallel systems only)

 

 

 

 

12

(X013)

Service bypass

Service bypass switch active

 

 

operation

 

 

 

 

13 ## (X014)

Boost charge

UPS boost-charging on battery

 

 

operation

 

 

 

 

 

14

(X015)

Battery voltage

DC voltage too high (shut down)

 

 

outside limits

DC voltage below warning level

 

 

 

DC voltage too low (shut down)

 

 

 

 

15

(X016)

Battery condition

ABM has detected weak battery condition

 

 

fault

ABM has detected defect battery

 

 

 

(ABM = Advanced Battery Monitor)

 

 

 

16 ## (X017)

Common fault

All alarms as mentioned above

 

 

 

(except relays 8+9+10+11)

 

 

 

Internal power supply fault

 

 

 

System locked in operation mode

 

 

 

Internal memory fault

 

 

 

Internal communication fault

 

 

 

 

##Delay programmable in configuration stack : “Common fault delay”. Settings 0,10,20,30 seconds.

990-4056

16

Installation Guide APC Silcon 240-320kW 400V UPS

Page 16