Options/Accessories

6.5Remote Display

With the remote display unit data may be displayed at distances of up to 25 m from UPS. For extended communication distance, see section below.

Remote display may easily be connected to UPS via one of the two serial communication ports on the communication interface board.

To obtain a transmission distance of up to 3.2 km normal RS232C signal levels must be converted to a long distance communication standard. The converter must be placed outside the UPS cabinet.

6.5.1 Extension of Remote Display Communication Distance

Remote display communicates with the UPS through a 3-wire RS232 interface. Remote display is a DTE (Data Terminal Equipment) employing a SUB-D 9-pin female connector. Communication speed: 9600 bps.

For communication distances, see Table 1. Insert converters if longer distances are necessary, or if communication cables are led through magnetically noisy areas. Converters must comply with local regulations

Table 1: Remote Display Communication Extensions

 

Standard

Short-haul

 

(RS232)

Modem Async

 

 

 

Max. distance

80/25 ft/m

10000/3200 ft/m

 

 

 

Converter Manufacture

No converter

BLACK BOX

Art. Code

 

ME800A-R2

 

 

 

RS232 BLACK BOX connector

 

Sub-D 25-pin female

 

 

 

BLACK BOX interconnector

 

4-screw terminal

 

 

 

Two converter boxes are required for a communication distance extension: One

box near the UPS for the conversion from RS232C to a long distance communication standard, and another box at the other end to convert back to RS232C, which is to be connected to the

990-4056

56

Installation Guide APC Silcon 240-320kW 400V UPS

Page 56
Image 56
American Power Conversion AP9604S manual Extension of Remote Display Communication Distance